Rheem BACnet MS-TP Скачать руководство пользователя страница 1

BACnet MS-TP Configuration Guide

Rheem Commercial Heat Pump BMS Card

Содержание BACnet MS-TP

Страница 1: ...BACnet MS TP Configuration Guide Rheem Commercial Heat Pump BMS Card...

Страница 2: ...g Go to BMS configuration will time out after 5 minutes if no buttons pressed Change the settings for BMS configuration from the display menu as mentioned below Address No change required address is i...

Страница 3: ...OK card ON LINE slow red OFF red if communication has not been established with the card card OFF LINE green red green if card detects errors or a temporary lack of response Network LED The Network L...

Страница 4: ...nds until the Status LED begins to flash SLOWLY 3 times red OFF 2 You will need to release the button before the 3rd red flash 3 After about 35 seconds the status LED will flash regularly and the card...

Страница 5: ...Right click on the USB serial port and open properties 9 Confirm that the port settings have the following values Bits per second 38400 Data Bits 8 Parity None Stop Bits 2 Flow control None 10 If requ...

Страница 6: ...Once in the pCONet SE section select the BACSet folder This will then allow the user to download the files BACSet_INSTALLER and BACSet_2 15 5 exe Install the program in the BACSet_INSTALLER folder fir...

Страница 7: ...How to Install BACset version 2 15 4 7...

Страница 8: ...Card Configuration via Laptop PC 11 Open up the BACSet program 12 Select MS TP a nd No Router and press OK 8...

Страница 9: ...lete Both LEDs will flash on the convertor 14 Once the read is complete you will see some text stating that the device was started in Factory Mode until next reboot This will allow you to make changes...

Страница 10: ...vice Instance based on the customer s network 16 Select the Write button 17 A warning message with pop up as shown below Select Yes to confirm the BACnet configuration overwrite 18 Wait for the progre...

Страница 11: ...C 19 Change the enable selection back to Disable Device Instance 20 Select and change the MS TP Station Address to the desired value 21 Select Write again and watch the status change from 0 back to 10...

Страница 12: ...PC 22 Change the MS TP Baud Rate to the desired value 23 Select Write again and watch the status change from 0 back to 100 and confirm Write Complete Note If finalised you may reboot the card for the...

Страница 13: ...elect the Test tab and read the values from the heat pump controller display 25 If no values appear confirm that the BMS settings on the heat pump display have the Protocol set to CAREL and the Speed...

Страница 14: ...BACnet MS TP Common Errors For further assistance call Rheem Service on 131 031 14...