INSTALLATION INSTRUCTIONS 

RHEEM FLUE TERMINAL DIVERTER  

WITH HEAT SHIELD (PN 299287) 

RHEEM EXTENDED FLUE TERMINAL DIVERTER 

WITH HEAT SHIELD (PN 299285) 

 
This instruction details the installation of the Rheem Flue Terminal Diverter with Heat Shield (PN 299287) and 
the  Rheem  Extended  Flue Terminal Diverter with Heat Shield (PN 299285) to  the  Rheem Electronic 
Continuous Flow Gas water heater models noted below (refer to the rating plate for model number): 
 

 

874826NF, 874T26NF

 

(26L/min 60°C, Natural Gas, Frost Protected) 

 

876826NF, 876T26NF

 

(26L/min 50°C, Natural Gas, Frost Protected) 

 

 Warning:

 Fitting of a Flue Terminal Diverter or Extended Flue Terminal Diverter to Rheem models other 

than those identified above can result in a potentially unsafe condition. 
 

SETTING BURNER GAS PRESSURE OF THE WATER HEATER 

It is necessary to check the burner gas pressure at both the minimum and maximum operational settings. To 
check and if necessary adjust the operational gas pressures, the electrical supply to the water heater must be 
switched on, the burners ignited and hot water must be flowing from a hot tap. 
 

 Warning:

 The removal of the front panel will expose 240 volt wiring. Take care not to touch wiring terminals. 

 

Note:

 If an 874 series model is installed as an in-series gas booster for a solar water heater, then during this 

procedure the temperature of the water entering the in-series gas booster must be below 58°C. Otherwise the 
gas burners will not ignite and the operational gas pressures cannot be measured. 
 

1. 

Close any hot taps and ensure the burners are not operating. 

2. 

Turn off the controller(s), if one is fitted, by pressing the on / off ( ) button and switch off the electrical 
supply at the power outlet to the water heater. 

3. 

Remove the top and bottom cover strips to gain access to the front cover screws by pressing on the two 
ridged finger points and gently pulling forward. 

4. 

Remove the screws holding the front panel to the jacket. 

5. 

Gently disengage the front panel and pull forward to remove 
from the water heater. 

6. 

Locate the burner pressure test point on the main burner 
manifold 

 

Remove the test point screw and washer from the test 
point orifice. 

 

Connect the manometer. 

7. 

Switch on the electrical supply at the power outlet to the water 
heater and turn on a controller, if one is fitted, by pressing the 
on / off ( ) button. 

8. 

The priority light and the on / off operating light will both glow. 

9. 

Open the gas isolation valve fully at the gas inlet to the water 
heater, if not already open. 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 