TM049 27L Continuous Flow Service Instructions
REV AL
– Issued April 2019
This document is stored and maintained electronically by Rheem Technical Support.
All printed copies are deemed “uncontrolled”.
32
CLEARING ERROR CODE HISTORY
Voltages up to 240 volts will be present within the water heater, take care
not to touch wiring terminals. Use an insulated tool when operating the
DIP switches or MIN and MAX buttons.
After repairing the water heater the existing error code history should be cleared. This will
allow fresh data to be stored and reduce the risk of confusion should it be necessary to
service the water heater in the future.
To clear the error code history:
1. Ensure all controllers (if fitted) are turned off and all hot taps are closed.
2. Remove the front panel of the water heater.
3. Ensure all DIP SWITCHES are in the off position (down position).
4. On the DIP1 set of switches, turn DIP SWITCH 1 on (up position) and then off (down
position) again.
5. Within 5 seconds of turning DIP SWITCH 1 off, press and hold either the MIN or MAX
button for more than 2 seconds.
6. Verify clearing of fault history by entering Maintenance Mode and check the code at
location 1E; it should read -- (no record)
7. Refit the water heater front panel.
RESETTING ERROR CODES
Most error codes can be reset by shutting off the hot water flow and turning the controllers
(if fitted) off and then on again. It may also be necessary to isolate and restore the power.
Where controllers are not fitted it may be necessary to turn the power off at the water heater
to clear the error code.
To reset Error Code 99 it is necessary to:
1. Ensure all controllers (if fitted) are turned off and all hot taps are closed.
2. Ensure all DIP SWITCHES are in the off position (down position).
3. Turn DIP SWITCH 2 on (up position) and then off (down position).
4. Within 5 seconds of turning DIP SWITCH 2 off, press and hold both the MIN and MAX
buttons for more than 2 seconds.
‘UL’ will flash on display and will become solid once
the 2 second period has expired.
5. Open and close a hot tap to complete the reset procedure.
6. Refit the water heater front panel.