Radio Frequency Systems
BD210WLP Series Air Dryer User’s Guide
Page 98 of 101
100518832 – Rev. B
14.4 SNMP Parameters
Device Configuration Information
Device ID
Alphanumeric (Defined by Customer)
Device Model
Alphanumeric (Factory Preset)
Device Firmware Version
Numeric (Factory Preset)
Current Date/Time
Numeric (mm/dd/yy hh:mm)
IP Address
Numeric (xxx.xxx.xxx.xxx)
Subnet Mask
Numeric (xxx.xxx.xxx.xxx)
Gateway Address
Numeric (xxx.xxx.xxx.xxx)
SNMP Trap Server Address
Numeric (xxx.xxx.xxx.xxx)
SNMP Read Community String
(also sets SNMP Trap Community String)
Alphanumeric (6-14 digits, Default =
“public”)
SNMP Write Community
Alphanumeric (6-14 digits, Default =
“123456”
Status Readings (Read-Only)
Outlet Pressure Reading
Numeric (PSI (KPa))
Tank Pressure Reading
Numeric (PSI (KPa))
Humidity Reading
Numeric (%)
Cabinet Temperature Reading
Numeric (DEG F (DEG C))
Duty Cycle Reading
Numeric (%)
Compressor Total Run Time Reading
Numeric (Hours)
Compressor Last Run Time Reading
Numeric (Seconds)
System Status
ON / SHUTDOWN
Compressor Status
ON / OFF
Fan Status
ON / OFF
Alarm Readings (Read-Only)
High Humidity Alarm
OK / Alarm
High Outlet Pressure Alarm
OK / Alarm
Low Outlet Pressure Alarm
OK / Alarm
High Cabinet Temperature Alarm
OK / Alarm
Duty Cycle Alarm
OK / Alarm
High Compressor Last Run Time Alarm
OK / Alarm
Maintenance Required Alarm
OK / Alarm
Total Alarm
OK / Alarm
Configuration Settings (Read-Write)
High Humidity Alarm Threshold
Numeric (%)
High Outlet Pressure Alarm Threshold
Numeric (PSI (KPa))
Low Outlet Pressure Alarm Threshold
Numeric (PSI (KPa))
Duty Cycle Alarm Threshold
Numeric (%)
High Compressor Last Run Time Alarm Threshold
Numeric (Seconds)
Reset Compressor Total Run Time Reading
Numeric (Hours)
Start Up Delay
Numeric (Seconds)
Alarm Reset
RESET
Alarm Delay
ON / OFF
Alarm Traps Sent to SNMP Server
High Humidity
High Outlet Pressure
Low Outlet Pressure
High Cabinet Temperature
High Duty Cycle
High Compressor Last Run Time
Maintenance Required
Содержание BD210WLP Series
Страница 2: ......