Radio Frequency Systems
BD210WLP Series Air Dryer User’s Guide
Page 97 of 101
100518832 – Rev. B
14.3 Set Point Limits and Defaults
14.3.1
System Adjustments
14.3.2
Alarm Set Points
Description
Minimum
Value
Maximum
Value
Default
Value
Unit of
Measurement
Shutdown
High Outlet Pressure
Alarm
0.30
(2.1)
7.50
(51.7)
7.50
(51.7)
PSI
(KPa)
Low Outlet Pressure
Alarm (LP UNITS)
0.30
(2.1)
7.50
(51.7)
0.30
(2.1)
PSI
(KPa)
High Humidity Alarm
3
15
10
%
YES
High Duty Cycle Alarm
0
99
70
%
High Compressor Last
Run Time Alarm
2:00
10:00
5:00
Minutes
High Cabinet
Temperature Alarm
120
(49)
DEG F
(DEG C)
YES
Compressor Total Run
Time Alarm
4,000
Hours
14.3.3
System Operations
Description
ON Value
OFF Value
Default
Value
Unit of
Measurement
Compressor
20 (137.9)
50 (344.7)
PSI (KPa)
Fan
90 (32.2)
80 (26.7)
DEG F (DEG C)
Description
Minimum
Value
Maximum
Value
Default
Value
Unit of
Measurement
System Pressure
50 (344.7)
PSI (KPa)
Outlet Pressure
0.30 (2.1)
7.5 (51.7)
PSI (KPa)
Alarm Delay
OFF
ON
ON
Содержание BD210WLP Series
Страница 2: ......