5. Power and Ethernet Connections
The following section describes how to connect power to the RFL3200 UK-10.
Before beginning the installation note the following:
•
Before proceeding with the connection of power to the RFL3200 UK-10 ensure that the power
wires to be installed are disconnected at their source.
•
Ensure that the power supply installed in your RFL3200 UK-10 will operate at the
available input power.
•
Follow all of your company’s policies and procedures regarding the installation of AC powered
or DC powered equipment. If there is a conflict between any procedure in this Users Guide
and your company’s safety rules, then your company’s safety rules must take priority.
Connecting Power
The RFL3200 UK-10 has a label located on the rear of the unit above the compression block that
indicates which power supply was installed in the unit before leaving the factory.
Before proceeding with the power and ground wire installation check the power supply label to
ensure that the unit will operate at the input voltage available.
WARNING!
The RFL3200 UK-10 must be properly grounded as described on the following page before
attempting to connect input power. Improper ground connections may result in system
malfunctions, equipment damage, or electrical shock.
For DC operations and AC operations where neutral cannot be reliably identified, readily accessible
double pole disconnects and overcurrent devices must be installed between the building wiring and
the RFL3200 UK-10.
For AC operations where the neutral can be reliably identified, readily accessible single pole
disconnects and overcurrent devices must be installed between the building wiring and the
RFL3200 UK-10.
RFL3200 UK-10 User Guide
RFL Electronics Inc.
October 6, 2010
9