Commissioning
GARD 8000 Distance Relay
RFL Electronics Inc.
12.12
DISTANCE RELAY FUNCTIONAL TESTING
The GARD8000 Distance Relay can be programmed with 4 Groups of settings. Each group can be
set independently with custom designed settings. Unless specifically requested during an initial
ordering of the equipment,
Group 4
is programmed in the factory with the default settings. The
Group 4 settings can be used to perform basic functional testing of the Distance Relay.
This commissioning procedure covers the following BASIC tests:
A, B, C Phase to Ground
3 Phases to Ground
A to B Phase
A to C Phase
3 Phase
Before proceeding with any of these tests verify the Factory Default settings for Group 4.
The factory programmed Group 4 settings are accessible under “Settings,” > “Chassis
Configuration,” “Distance Relay,” “General Settings” and “Active Setting Group,” select group
4 and click on “Save.”
During functional testing the Distance Relay SOE records, GARD8000 System SOE records
and Distance Relay Oscillography can be retrieved for an evaluation.
March 1, 2009
12-10
973.334.3100
Содержание GARD 8000
Страница 14: ...GARD 8000 Distance Relay RFL Electronics Inc This page intentionally left blank April 1 2010 xiv 973 334 3100...
Страница 229: ...Distance Relay Logic Programming GARD 8000 Distance Relay RFL Electronics Inc March 1 2009 11 21 973 334 3100...
Страница 231: ...Distance Relay Logic Programming GARD 8000 Distance Relay RFL Electronics Inc March 1 2009 11 23 973 334 3100...
Страница 270: ...Application Notes GARD 8000 Distance Relay RFL Electronics Inc March 1 2009 14 2 973 334 3100...