2. Connecting Alarm Relays and Power
The following section describes how to connect Alarm Relays and Power to the eXmux 3500M.
Before beginning the installation note the following:
•
RFL recommends that wires only be terminated with ring lugs.
•
The specified operating temperature of the eXmux 3500M is -30
°
C to +65
°
C
(-22
°
F to +149
°
F). Operation at higher temperatures may affect system reliability and
performance. Systems installed in enclosed cabinets should be well ventilated.
A full 1U of
chassis space must be left open above the installed eXmux 3500M.
•
Before proceeding with the connection of power to the eXmux 3500 ensure that the main and
redundant power supply switches are in the “OFF” position, and that the power wires to be
installed are disconnected at their source.
•
All relay contacts are labeled in the de-energized position.
•
Ensure that the power supply(ies) installed in your eXmux 3500M will operate at the
available input power.
•
Follow all of your company’s policies and procedures regarding the installation of AC powered
or DC powered equipment. If there is a conflict between any procedure in this Quick Start
Guide and your company’s safety rules, then your company’s safety rules must take priority.
CAUTION
Any installation using an enclosed cabinet with a swing-out rack must be securely fastened to the
floor. This will prevent the cabinet from falling forward when the rack is moved outward.