AVANTAGE DP

Motorised dual purpose CE marked AOV for protected

lobby to shaft ventilation.

Содержание AVANTAGE DP 1V120

Страница 1: ...e Distributed in the UK and Ireland by Smoke Control Dampers Ltd 6 Avon Gorge Industrial Estate Avonmouth Bristol BS11 9LQ T 44 0 117 938 1666 sales smokecontroldampers co uk AVANTAGE DP Motorised dua...

Страница 2: ...utomatic activation multi multiple 1500 pressure level 3 1500Pa ved vertical duct hod horizontal duct V volt W watt V AC Volt alternating current V DC Volt direct current E ALIM power supply magnet E...

Страница 3: ...roc F V500 35mm 1 EI 60 v ed i n o S 500 C10000 AA multi Avantage 120 Promatect L500 50mm 1 EI 120 v ed i n o S 500 C10000 AA multi Geoflam 45mm 1 EI 120 v ed i n o S 500 C10000 AA multi Geoflam Light...

Страница 4: ...acuate smoke in emergency situations whilst maintaining fire resistant integrity in standby position 5 5 simple operating tests through remote opening and resetting 5 5 optimal free air passage and mi...

Страница 5: ...DC KITS FDC VA Volt free switches for remote signalling of open and closed damper position KITS ME AVANDP Motor DP 24V Options at the time of order BLACK Damper painted black with non decorated dust...

Страница 6: ...con structed from similar materials with a fire resistance thickness and density equal or superior to these of the tested materials Caution when fitting the product should be handled with care and re...

Страница 7: ...tch locates with the strike plate Electrical connection The DP drive motor is a 24 volt DC 0 8 amp rated motor that requires a 24 volt 5 fully smooth and rectified supply The damper operates on a 2 wi...

Страница 8: ...t the chosen corner s The galvanised part at the inside of the shutter is already indented Caution after passing and fixing the cables it is necessary to caulk around the electrical cables with fire r...

Страница 9: ...differently installed in the shaft in the axis of the shaft or outside the shaft or shaft extension Maintenance No specific maintenance required Schedule at least two running checks each year Remove d...

Страница 10: ...n 4 Motor drive arm 5 Cable connectors 4 2 1 3 5 Unlocking manual unlocking manual release with the damper key remote unlocking remote by connection of 24 V DC Resetting manual resetting rearm magneti...

Страница 11: ...6 8 17 7 18 6 925 kg 12 9 13 6 14 4 15 1 16 2 17 2 18 1 19 0 955 kg 13 1 13 9 14 7 15 4 16 5 17 5 18 5 19 5 985 kg 13 4 14 2 15 0 15 7 16 9 17 9 18 9 19 9 1015 kg 13 6 14 4 15 3 16 0 17 2 18 2 19 3 20...

Страница 12: ...kg 13 6 14 4 15 3 16 0 17 2 18 2 19 3 20 3 1045 kg 13 9 14 7 15 5 16 2 17 5 18 6 19 6 20 7 1075 kg 14 1 15 0 15 8 16 5 17 8 18 9 20 0 21 1 Selection graphs Avantage 1V v m s p Pa 300 350 400 450 500...

Страница 13: ...5574 0 5082 0 4672 0 4325 685 0 8789 0 754 0 6609 0 589 0 5316 0 4848 0 4457 0 4127 715 0 8394 0 7204 0 6315 0 5629 0 5082 0 4635 0 4262 0 3946 745 0 8034 0 6897 0 6048 0 5392 0 4868 0 444 0 4083 0 37...

Страница 14: ...0 2601 0 2942 0 3284 0 3625 0 3967 0 4308 775 Sn m 0 2005 0 2361 0 2719 0 3075 0 3432 0 3788 0 4145 0 4501 805 Sn m 0 2093 0 2465 0 2837 0 3209 0 3580 0 3952 0 4323 0 4695 835 Sn m 0 2181 0 2568 0 295...