background image

19

I-RIH (05-21) 131793-A

OPERATION

Pre-Startup Checklist

 

‰

Ensure that electrical supply matches voltage of unit .

 

‰

Check for proper grounding and polarity of the ignition system . The direct spark ignition system cannot determine 

the presence of flame and will lockout and shut off if it is not electrically grounded to the burner .

 

‰

Ensure that all clearances to combustibles are maintained .

 

‰

Check the location of sprinkler heads—high temperature heads may be required .

 

‰

Space directly below the heater should be free of objects that may overheat or prevent infrared energy from 

reaching desired area .

 

‰

Post signs indicating maximum stacking height under or near heater .

 

‰

Heater may be angle-mounted only as specified .

 

‰

Ensure that heater is level and is suspended in accordance with 

Suspension Mounting

 section .

 

‰

Ensure that there are no gas or electric lines above or below the heater .

 

‰

Adequate ventilation MUST be provided .

 

‰

Gas piping and supply must meet requirements .

 

‰

Ensure that all air has been purged from the gas supply line .

 

‰

Complete the installation record on the back page of this manual .

 

‰

Keep this manual for future reference .

Startup

⚠ CAUTION ⚠

IMPORTANT: The control system cannot determine the presence of flame and the control system 

will lockout and shut off if it is not electrically grounded to the burner. The control is extremely 

polarity sensitive. Proper grounding and proper electrical polarity are essential to the operation 

of these heaters.

Light the heater as folows:
1 .  Turn manual gas valve to OFF position .
2 .  Turn electrical supply OFF .
3 .  Wait at least 5 minutes and then set thermostat above room temperature .
4 .  Turn manual gas valve to ON position .
5 .  Turn electrical supply ON .
6 .  Set thermostat to desired temperature .
7 .  If heater does not light, repeat steps 1 through 6 .

Sequence of Operation

1 .  Thermostat calls for heat—on two-stage models, low-heat or high-heat operation is determined by thermostat 

setpoints—refer to thermostat manufacturer’s instructions .

2 .  Power is applied to the Ignition Detection Control (IDC)—15 seconds after power is applied, a spark is developed 

at the electrodes and the combination gas valve opens for a 15-second trial-for-ignition period .

3 .  Burner ignites—a small DC electrical current begins flowing from the sensing electrode through flame to ground .
4 .  The controller senses current and turns OFF spark—gas continues to flow through the combination gas valve—

sparking may continue for the full 15 seconds before stopping .
a .  If the burner fail to light or if flame is not detected during the first trial-for-ignition period, the combination gas 

valve is de-energized and the controller starts the 15-second inter-purge sequence before another ignition trial .

b .  After 15 seconds, the controller begins two (2) more ignition trials .
c .  If the burner fails to light after the third trial, the controller will de-energize the gas valve and go into lockout mode .

Содержание RIHL

Страница 1: ...u la mort Read these instructions thoroughly before installing or servicing this equipment Lisez attentivement les instructions d installation de fonctionnement et d entretien avant de proc der l inst...

Страница 2: ...with 24VAC Direct Spark Ignition DSI Single Stage Controls 15 Wiring for Units with 24VAC Direct Spark Ignition DSI Two Stage Controls 16 FIELD INSTALLED OPTIONS 17 Thermostat Option CL34 17 Thermost...

Страница 3: ...ss DANGER A danger statement describes a potentially hazardous situation that if not avoided will result in severe personal injury or death and or property damage WARNING A warning statement describes...

Страница 4: ...micile intended for use by one or more persons and that includes one or more areas such as those used for cooking eating living sleeping or a sanitary facility A residential dwelling does not include...

Страница 5: ...the area is within the clearance to combustible material as marked on the heater rating plate Both NFPA 409 latest edition and CAN CSA B149 1 latest edition specify a minimum clearance of 8 feet 2 5...

Страница 6: ...ater cannot operate unless the supply and exhaust system is operating Mechanical exhaust fans are typically located at high points of the building For flat roof areas a series of small exhausters shou...

Страница 7: ...learances between the combustion surface and combustibles The stated clearance to combustibles represents a surface temperature of 90 F 50 C above room temperature If the unit must be close to the roo...

Страница 8: ...8 68 1727 140 3556 180 4572 Propane RIHL 050 30 762 60 1524 80 2032 48 1219 34 864 110 2794 RIHVL 090 36 914 30 762 62 1575 105 2667 50 1270 38 965 135 3429 120 46 1168 33 838 64 1635 125 3175 58 1473...

Страница 9: ...24 5 6 6 7 5 160 25 0 28 5 7 7 8 7 22 5 25 5 6 9 7 8 200 27 0 31 0 8 2 9 4 24 5 28 0 7 5 8 5 Table 6 Recommended Distances for Units Mounted at 5 Degree Angle Model Unit Size Reflector Type Maximum Di...

Страница 10: ...d at 5 or 30 degrees The heater is NOT design certified for use above 30 degrees and voids the manufacturer s warranty as well A horizontal or zero degree angle is not recommended because flue gases c...

Страница 11: ...e Piping joint compound must be resistant to the action of liquefied petroleum gases DO NOT install any gas piping in heat zones CAUTION All piping must be installed according to local codes Use new c...

Страница 12: ...ion immediately upstream of the gas supply connection to the heater see Figure 4 Test all piping joints for leaks using a non corrosive leak detecting solution Do not subject gas pressure regulators f...

Страница 13: ...the Canadian Electrical Code CSA C22 1 latest edition Theelectricalsupplywiringtotheheatersusing120VACor24VACmustbeinstalledinaccordance with local codes or the National Electric Code ANSI NFPA 70 la...

Страница 14: ...ng a temperature rating of at least 302 F 150 C and a minimum size of 16 AWG 1 0 mm2 Si l un des c bles d origine fournis avec cet appareil doit tre remplac le remplacer par un c ble convenant pour un...

Страница 15: ...ol is polarity sensitive GND 24 GGS BL BL GGS VR SW MV LEGEND 24 24 VAC Supply Voltage GND Earth Ground MV Mechanical Ventilation VR Ventilation Relay SW Ventilation Interlock Switch normally opened G...

Страница 16: ...polarity sensitive Field wiring Thermostat cable 18 4 18AWG 0 8 mm2 4 conductor solid class 2 Minimum insulation temperature 140 F 60 C between thermostat and heater Maximum length 125 feet 38 meters...

Страница 17: ...its use The installer user owner employer must determine the specific safety requirements The specific safety requirements will vary depending on the location and operating procedures Therefore approp...

Страница 18: ...entrance of foreign objects This option is not for use with a parabolic reflector option DM2 If a protective screen is required with a parabolic reflector contact the factory Figure 13 Protective Scr...

Страница 19: ...itive Proper grounding and proper electrical polarity are essential to the operation of these heaters Light the heater as folows 1 Turn manual gas valve to OFF position 2 Turn electrical supply OFF 3...

Страница 20: ...seconds Shutdown To shutdown the heater for one week or less turn OFF electrical supply to heater for more than one week turn OFF electrical supply to heater and turn OFF gas supply at gas isolation...

Страница 21: ...re 15 DETAIL B 3 Check to ensure that there is spark gap clearance of 0 219 0 032 inches 5 6 mm from ceramic tile surface to the sparking tips of electrode direct spark assembly see Figure 15 DETAIL C...

Страница 22: ...r is applied Replace combination gas valve 7 Supply manifold gas pressure too low Adjust pressure in accordance with rating plate 8 Ignition detection control defective Replace ignition detection cont...

Страница 23: ...nturi obstructed by spider web Clean venturi using bottle brush 2 Foreign matter in venturi Check and clean in accordance with Annual Maintenance section 3 Orifice partially blocked 4 Supply gas press...

Страница 24: ...________________________________________ ________________________________________________________ Phone ________________________________________________________ Model ________________ Serial No ______...

Отзывы: