NOTICE

:

The information contained on the following page(s) was produced 

prior to May 1, 2014. On that date Reznor became part of

Nortek, Inc.

References to any other company affiliations are no longer valid.

This manual refers to Reznor brand products that have been

discontinued for more than 10 years.

Some replacement parts may no longer be available from

our suppliers. Compatible parts may be substituted.

Please contact your Reznor Representative

with specific questions.

©2014 Reznor, LLC. All Rights Reserved.

Trademark notice: Reznor is registered in at least the United States.

0514  PDF  Form Cover2

Содержание INFRA-REZ TR

Страница 1: ...alid This manual refers to Reznor brand products that have been discontinued for more than 10 years Some replacement parts may no longer be available from our suppliers Compatible parts may be substit...

Страница 2: ...paragraphs which follow discuss the components and systems that require routine inspection maintenance At the beginning of each section there is a code indicating the main reason why that maintenance...

Страница 3: ...ustion air inlet terminal for any restric tions and or damage Clean if restricted and replace if damaged 6 Combustion Air System and Main Burner During an average heating season approximately 65 ton o...

Страница 4: ...he burner tube will cause gas odor inside the building and if not corrected could eventually cause a fire explosion hazard To prevent fuel gas spilling from the back of the burner tube clean the main...

Страница 5: ...h Pilot bracket may remain attached to the burner control box Ground Rod Service Section Control Location Operation and Service WARNING Service work on this heater should only be done by a qualified g...

Страница 6: ...l vary slightly depending on inlet and or outlet restric tions Sensing Pressure Check requires a sensitive slope gauge several feet of 3 16 O D rubber tubing and two 1 4 O D barbed tees 1 Disconnect t...

Страница 7: ...trode and pilot burner hood Refer to Maintenance Section Paragraph 8 for cleaning instructions 3 Dirty or restricted pilot orifice Refer to Maintenance Section Paragraph 8 for instructions on cleaning...

Страница 8: ...may not occur The result is incomplete combustionwhichproducescarbonmonoxide apoisonousgasthatcancausedeath Thesetubularinfrared heaters may be safely operated in the vented or unvented mode FAILURE T...

Страница 9: ...to pressure switch Troubleshooting Guide Figure 18 Is voltage present at motor terminals on time delay Refer to Service Section Time Delay Relay Pargraph 9 Replace combustion air blower motor Replace...

Страница 10: ...Replace the ignition controller Is the gas supply pressure correct refer to Table 3 Paragraph 11 New installations Be certain air is completely bled from the gas line Clean pilot orifice using compre...

Страница 11: ...itch New Installations Check for excess vent and or combustion air inlet pipe or incorrect vent and or combustion air inlet components Refer to Installation Manual Venting Paragraph 11 and Combustion...

Страница 12: ...Form RZ NA O TR Mfg No 121028 Rev 7 Page 11 17 Wiring Diagram...

Страница 13: ...c com 2004 All rights reserved Printed in the U S A MANUFACTURER OF GAS OIL ELECTRIC HEATING AND VENTILATING SYSTEMS Trademark Note Reznor and INFRA REZ are registered in the United States and other c...