Form I-XE/CRGB/RPB, Mfg No. 131782 Rev 4, Page 43

Loosen Screws

Remove

Screws

Tube Baffle Holddown Plate

Rear Baffle

Front

Baffle

Tube

Baffle

FIGURE 50 - Remove "V" Baffles to Clean Inner Surface
of Heat Exchanger Tubes

Indoor, Gravity Vent Models XE/HXE (See FIGURE 50)

1) Remove the screws (the number varies depending on unit size)

along the bottom of the front baffle and the three on each end.
Slide the front baffle out of the furnace.

2) Remove the screws that attach the tube baffle hold-down plate to

the rear flue baffle.

3) Pull the "V" baffles out of the heat exchanger.

All Models

 - Clean the inner surfaces of the heat exchanger from be-

neath using the brush to "scrub" the tube walls to remove any accumu-
lated dust, rust and/or soot. Clean the "V" tubes and re-assemble the
heat exchanger and the furnace.

Check the furnace for proper operation.

41. Troubleshooting

Troubleshooting the System

TROUBLE

PROBABLE CAUS E

REMEDY

1.

 No power to the furnace.

1. 

Turn on power, check supply fuses or circuit breaker.

2.

 No 24-volt power to venter relay.

2.

 Turn up thermostat, check control transformer output. Check for loose or improper 

wire connections.

3.

 Venter relay defective.

3.

 Replace.

4. 

Defective motor or capacitor.

4.

 Replace defective part.

1.

 M anual valve not open.

1. 

Open manual valve.

2.

 Air in gas line.

2.

 Bleed gas line.

3.

 Dirt in p ilot orifice.

3.

 Remove and clean with compressed air or solvent (do not ream). 

4. 

Gas pressure too high or too low.

4.

 Adjust supp ly pressure. (See Paragraph 11). 

5. 

 Kinked pilot tubing.

5.

 Replace tubing.

6.

  Pilot valve does not open.

6.

 If 24 volt available at valve, replace valve. 

7.

  No spark:

7. 

a)

 Loose wire connections

a) 

Be certain all wires connections are solid.

b)

 Transformer failure.

b)

 Be certain 24 volts is available. 

c) 

Incorrect spark gap.

c)

 M aintain spark gap at 7/64".

d) 

Spark cable shorted to ground.

d)

 Replace worn or grounded spark cable. 

e) 

Spark electrode shorted to ground.

e) 

Replace pilot if ceramic spark electrode is cracked or grounded. 

f) 

Drafts affecting pilot.

f)

 M ake sure all panels are in place and tightly secured to prevent  drafts at pilot. 

g)

 Ignition control not grounded.

g)

 M ake certain ignition control is grounded to furnace chassis.

h) 

Faulty  ignition controller.

h) 

 If 24 volt is available to ignition controller and all other causes have been eliminated, 

replace controller.

8.

 Optional lockout device interrupting control circuit by above causes.

8.

 Reset lockout by interrupting control at thermostat.

9.

 Faulty combustion air proving switch. 

9.

 Replace combustion air proving switch. 

10.

 Activated blocked vent switch (indoor sy stem)

10. 

Correct venting problem. Reset switch.

1. 

M anual valve not open.

1.

 Open manual valve.

2. 

M ain valve not operating.

2.

a) 

Defective valve.

a) 

If 24 volt is measured at valve connections and valve remains closed, rep lace valve.

b) 

Loose wire connections.

b)

 Check and tighten all wiring connections.

3. 

Ignition control does not power main  valve. 

3.

a)

 Loose wire connections.

a)

 Check and tighten all wiring connections.

b)

 Flame sensor grounded. (Pilot lights - spark continues)

b)

Be certain flame sensor lead is not grounded or insulation or ceramic is not cracked. 

Replace as required.

c)

 Gas pressure incorrect.

c) 

Adjust gas p ressure. (See Paragraph 11.)

d) 

Cracked ceramic at sensor.

d) 

Replace sensor.

e)

 Faulty ignition controller.

e) 

See Paragraph 25.  If all checks indicate no other cause, replace ignition controller. 

 Do 

not 

attempt to repair the ignition controller. This device has no field replaceable parts. 

f) 

Poor microamp  signal

f) 

Adjust pilot regulator

1.

 Dirty filters in blower system..

1.

 Clean or replace filters.

2.

 Incorrect manifold pressure or orifices.

2.

 Check manifold pressure (See Paragraph 11).

3.

 Cycling on limit control.

3. 

Check air throughp ut (See Paragrap h 13). 

4.

 Improper thermostat location or adjustment. 

4.

 See thermostat manufacturer's instructions. 

5.

 Belt slipping on blower

5. 

Adjust belt tension

6.

 Fan control improperly wired

6.

 Connect as per wiring diagram.

7.

 Defective fan control.

7. 

Replace fan control.

8. 

Blower set for too low temperature rise.

8.

 Slow down blower or increase static pressure.

1. 

Circuit op en

1. 

Check wiring and connections.

2. 

Fan Control inoperative

2. 

Replace fan control.

3.

 Fan control improperly wired

3.

 Connect as per wiring diagram.

4. 

Contactor inop erative

4. 

Replace contactor.

5.

 Defective motor.

5.

 Replace motor.

1. 

M otor overload device cycling

1. 

Check motor load against motor rating p lace. Replace motor or overload device.

2.

 3-phase motor rotating in opposite direction

2.

 Interchange two legs of supply connections.

1. 

Improper motor p ulley adjustment

1. 

See instructions on air throughput (See Paragraph 13).

2. 

Improper static pressure on duct system

2. 

Adjust dampers in duct system.

3. 

Low voltage

3. 

Check power  supp ly.

Pilot lights; main 
valve will not open. 

Pilot will not light. 
(Venter operating 
on power-vented 
models.)

Venter motor will 
not start.

Motor cuts out on 
overload

Motor will not run

No heat (Heater 
operating.)

Motor turns on and 
off while operating

Содержание CRGB Series

Страница 1: ...AquaSaver Timer Adjustment 34 Belts 24 Blocked Vent Switch 25 Blower Motors 24 Blower Rotation 24 Burner Air Adjustment 30 Burner Rack Removal 42 Burners 29 Carryover System 29 Check Installation and...

Страница 2: ...rhalogenatedhydrocarbonsorany contaminant silicone aluminium oxide etc that adheres to the spark ignition flame sensing probe b Wiring is not in accordance with the diagram furnished with the heater c...

Страница 3: ...x 19 1 2 495mm Return Air Openings with Optional Cabinet X Hanger Centerline Standard and Optional Blower Cabinet Dimensions inches andmm Gravity Vented Indoor Models XE HXE Gas Connection Natural Pr...

Страница 4: ...side the downturn plenum cabinet For dimensions with downturn plenum cabinet with a cooling coil cabinet see page 6 FIGURE1B Dimensions Outdoor Gravity VentedModel Series CRGB Vent Cap Gas Connection...

Страница 5: ...ottom of cabinet side If system has a cooling coil cabinet add length dimension on page 6 for full system length The two position discharge dampers in Option AQ8 fit in the discharge air opening The d...

Страница 6: ...ownturnPlenumCabinet factoryattachedto either type of Cooling Coil Cabinet Front View DX Coil Cabinet with Horizontal Discharge Option AU3 Liquid Line Connections 7 8 or 1 3 8 5 1 8 130 8 203 3 4 19 3...

Страница 7: ...r from inside the building openings 1 square inch free area per 1000 BTUH Never less than 100 square inches free area for each open ing See 1 in FIGURE 2 2 Air from outside through duct openings 1 squ...

Страница 8: ...the pipe hanger to a 1 threaded pipe See the suspension method on the left in FIGURE 4 As an alternative method the factory installed pipe hanger may be removed and the heater suspended as illustrated...

Страница 9: ...lled 1 Position curb cross rails and curb side rails as illustrated in FIGURE 8 page 10 If there are two side pieces to a side fasten them with splice plates and hardware as illustrated in the splicin...

Страница 10: ...e is horizontal If the system has an AU11 AU12 AU13 AU14 cooling coil cabinet there is a downturn plenum with vertical discharge Options AU2 AU3 AU11 AU12 AU13 and AU14 are not factory installed Optio...

Страница 11: ...should be supported every six feet 1 8M using a non combustible material such as strap steel or chain Do not rely on the drafthood or heater for support of either horizontal or vertical vent pipe 6 V...

Страница 12: ...re horizontal venting is required or where negative building pressure inhibits gravity venting in stall an optional power venter Option CA Use only a power venter provided by the furnace manufacturer...

Страница 13: ...mmended size is 1 2 x1 2 20 gauge FIGURE11B InstallationoftheVentCap includedinthe optionpackage andthefield suppliedPipingandSupports Oval Adapter Assy PN 103025 Venter Seal Plate P N 43446 9 Condens...

Страница 14: ...air duct should come in con tact with masonry walls Insulate around all air duct through ma sonry walls with not less than 1 2 1 is recommended of insula tion Through Unheated Space Insulate all expo...

Страница 15: ...l connections are made disconnect the pilot supply at the control valve and bleed the system of air Reconnect the pilot line and leak test all connections by brushing on a soap solution WARNING All co...

Страница 16: ...ding MUST be made in accordance with the National Electric CodeANSI NFPANo 70 latest edition or in Canada the Canadian Electrical Code Part I C S A Standard C22 1 In addition the installer should be a...

Страница 17: ...ontrols available as part of the gas and air control options Check the wiring diagram and literature supplied with the unit for operation of factory installed optional controls See FIGURE 19 for locat...

Страница 18: ...ND BLOWER MOTOR BRANCH CIRCUIT WIRE SHOULD BE SIZED TO TEMPERATURE RATING OF AT LEAST 105 C EXCEPT FOR MUST BE REPLACED IT MUST BE REPLACED WITH WIRING MATERIAL HAVING A 4 CAUTION IF ANY OF THE ORIGIN...

Страница 19: ...W LEADS CAP RED 8 USE 18 GA WIRE FOR 24 VOLT CONTROL WIRING ON UNIT NONE NOTES 4 CAUTION IF ANY OF THE ORIGINAL WIRE AS SUPPLIED WITH THE APPLIANCE MUST BE REPLACED IT MUST BE REPLACED WITH WIRING MAT...

Страница 20: ...L WIRE AS SUPPLIED WITH THE APPLIANCE 3 DOTTED WIRING AND THE FOLLOWING CONTROLS ARE SUPPLIED AND INSTALLED 2 THE FOLLOWING CONTROLS ARE SUPPLIED AS OPTIONAL EQUIPMENT 1 THE FOLLOWING CONTROLS ARE SUP...

Страница 21: ...N IF ANY OF THE ORIGINAL WIRE AS SUPPLIED WITH THE APPLIANCE 3 DOTTED WIRING AND THE FOLLOWING CONTROLS ARE SUPPLIED AND INSTALLED 2 THE FOLLOWING CONTROLS ARE SUPPLIED AS OPTIONAL EQUIPMENT 1 THE FOL...

Страница 22: ...E SAFETY SWITCH PORTION OF THE CONTROL THE SWITCH ACTION PROVES THE PRESENCE OF THE PILOT FLAME AND ENERGIZED THE A PILOT FLAME ON EACH OPERATING CYCLE THE SENSING PROBE ENERGIZING THE PILOT GAS VALVE...

Страница 23: ...ND ENERGIZES THE MAIN VALVE THE MAIN GAS IGNITES AND THE UNIT FIRES AT LOW RATE 3 ON A CALL FOR HEAT BY THE HIGH STAGE OF THERMOSTAT THE UNIT FIRES AT FULL RATE 4 IF THE FLAME IS EXTINGUISHED DURING M...

Страница 24: ...outlet temperature turn the adjustable half of the pulley outward One turn of the pulley will change the speed 8 10 5 Tighten the setscrew on the flat portion of the pulley shaft 6 Replace the belt an...

Страница 25: ...ing pressure levels off If a restriction or excessive flue length or turns cause the sensing pres sure to become less than the switch setpoint the pressure switch will function to shut off the main bu...

Страница 26: ...e same as the one illustrated 1 Remove the access panel in the ductwork adjacent to the control compartment access panel 2 Element is retained by spring clips 3 Round gasket and metal retaining plate...

Страница 27: ...IGURE24 Signal Conditioner used in Options AG21 and AG40 Carryover Regulator Modulating Valve Single Stage Gas PrimaryGas FlowPressure Switch WhiteLabel 1 1 w c GasFlow PressureSwitch WhiteLabel 1 1 w...

Страница 28: ...per open Is there voltage between Terminal 88 and Terminal 7 Is there voltage between Terminal 4 on ignition permissive relay and Terminal 7 Replace 1 time delay relay Replace ignition permissive rela...

Страница 29: ...6 38mm 79 23 32 18 25mm 7 16 1 16 11mm 1 6 Option AH2 and spark pilot with lockout is Option AH3 NOTE Outdoor units in Canada using propane require lockout Indoor units in U S and Canada using propane...

Страница 30: ...ers cont d INDOOR Gravity Vented Furnace Models XE HXE Natural gas burners are equipped with two flash carryover systems that receive a supply of gas simultaneously with the main burner NOTE A natural...

Страница 31: ...esuppliedwithairforcombustionasrequired by Code and in Paragraph 6A of this heater installation manual MAINTAIN THE VENT SYSTEM IN STRUCTURALLY SOUND AND PROPERLYOPERATINGCONDITION lockout control if...

Страница 32: ...3 Bottom Panel Position the air hood bottom panel so that it is to the inside of the two side panels and above the factory installed support angle Attach to the side panels If the bottom panel does n...

Страница 33: ...ecessary Follow these instructions to field connect the water supply and make neces sary checks and adjustments before operating the cooling module with a lock nut and a sealing gasket Check these fit...

Страница 34: ...ockwise to increase the ON time or counterclockwise to decrease the ON time One complete turn will adjust the cycle by 12 to 14 seconds All Modules Check the reservoir for any water leaks The reservoi...

Страница 35: ...e the water feed line from the downstream side of the ball valve and unscrew the water bleed line barbed hose fitting 3 Force a fresh water supply through the water inlet hose and thoroughly flush the...

Страница 36: ...let DamperOptionsonIndoor ModelsXE HXE FIGURE 41B Location of Controls for30 OutsideAirHood andDamperOptions AR6orAR7 OutdoorModelsonly FIGURE41D Exampleof OutsideAirand Return Air Damper Linkage Damp...

Страница 37: ...w c Heater Filter Size Metal Fillers Size A B C D E F1 F2 75 100 125 20x20 20x20 150 175 20x25 20x25 13 16 13 16 200 225 16x25 16x20 16x25 16x20 250 300 20x25 20x20 20x25 20x20 350 20x25 20x25 20x25...

Страница 38: ...B D D E 25 635mm 20 508mm 20 508mm 25 635mm Size 350 D D D C C Size 400 25 635mm 20 508mm B D Key Filter Code Filter Size A 16 x 20 B 20 x 20 C 16 x 25 D 20 x 25 E 25 x 25 Shaded areas are filter blo...

Страница 39: ...d with op tional discharge dampers the damper motor wires must be connected to the terminal blocks in the furnace electrical compartment If the coil cabinet being installed does not include a downturn...

Страница 40: ...ection remove the center hole plug FIGURE 46H To install side and top fillerpanels remove screws from top corners of both cabinets and the entire row across the cooling coil cabinet Removerowofscrews...

Страница 41: ...or lint accumulation Clean as needed Check the vent system for soundness Replace any parts that do not appear sound Check the wiring for any damaged wire Replace damaged wiring See Paragraph 12 for re...

Страница 42: ...ryover systems with air pressure 40 Cleaning the Heat Exchanger To clean the outer surfaces circulating air side of the heat exchanger gain access by removing the inspection panels in the ductwork or...

Страница 43: ...causes 8 Reset lockout by interrupting control at thermostat 9 Faulty combustion air proving switch 9 Replace combustion air proving switch 10 Activated blocked vent switch indoor system 10 Correct ve...

Страница 44: ...AG39 or AG40 see page 28 For replacement parts refer to Form P X XE for indoor units or Form P RG RP RBL for outdoor units Problem Probable Cause Remedy Pump does not run Unit is 1 Electrical connecti...

Отзывы: