background image

Form I-XE/CRGB/RPB, Page 42

Top Baffle

Support

Screws B

Bottom

Baffle Support

Brackets

Air

 Discharge

Dir

ection of 

Airflow

Screw C

Right

Left

Screws A

Scr

ew C

Flue Diverter

(Sizes 225-400 only)

Tube Baffle

Collection Box End

Blockoff Plate

Screw

Collection

Box End

Screw

FIGURE 48 -
When cleaning
outer heat
exchanger
surface, remove
directional
air baffles.
Remove Screws
"A" and slide
baffles out.
Clean and
replace all
baffles.
NOTE: High
CFM furnaces
do not have
directional air
baffles.

38. Burner Rack Removal

Instructions

1.

Turn off the gas supply.

2.

Turn off the electric supply.

3.

Remove control access side panel.

4.

Disconnect the pilot tubing and flame sensor lead (spark pilot).

5.

Mark and disconnect electric valve leads.

6.

Uncouple the union in the gas supply.

7.

Remove sheetmetal screws in the top corners of the burner
rack assembly.

8.

Pull "drawer-type" burner rack out of the furnace.

To disassemble the burner rack:
1. 

Remove Carryover System -

Natural Gas

 - Remove the flash carryover system from the

"manifold end" of the burner rack. 

NOTE: 

Natural gas burner

racks manufactured prior to 3/95 have a lighter tube carryover
system. Break the lighter tube connection at the orifice and re-
move the supply tubing, the drip shield and the lighter tube.

Propane Gas

 - Break the lighter tube connection at the regulator

and remove the lighter tube orifice supply tubing; remove the
retaining screws in the drip shield and the shield; remove the
retaining screws and slide out the lighter tube.

2.

Pull main burners horizontally away from injection opening
and lift out.

3.

Remove manifold bracket screws and remove manifold.

4.

Change main burner orifices, if necessary.

5.

Remove screws and lift out pilot burner.

Follow the instructions in Paragraph 39 to clean. To re-assemble and
replace, reverse the above procedures being careful not to create any
unsafe conditions.

CAUTION: When cleaning, wearing eye

protection is recommended.

39. Cleaning Pilot & Main Burners

In the event the pilot flame is short and/or yellow, check the pilot
orifice for blockage caused by lint or dust accumulation. Remove the
pilot orifice and clean with air pressure. DO NOT REAM THE
ORIFICE. Check and clean the aeration slot in the pilot burner.
Clean the metal sensing probe and the pilot hood with an emery
cloth and wipe off the ceramic insulator. Check the spark gap; spark
gap should be maintained to 7/64". After the pilot is cleaned, blow
any dirt away with compressed air. (See ignition requirements in
Paragraph 27.)
Clean the main burners with air pressure. Use an air nozzle to blow
out scale and dust accumulation from the burner ports. Alternately
blow through the burner ports and the venturi. Use a fine wire to
dislodge any stubborn particles. Do not use anything that might
change the port size.
Clean the burner rack carryover systems with air pressure.

40. Cleaning the Heat Exchanger

To clean the outer surfaces (circulating air side) of the heat exchanger,
gain access by removing the inspection panels in the ductwork or
remove the ductwork. Depending on whether or not the furnace is
designed for high CFM (Model prefix "H"), there may be directional
baffles between the heat exchanger tubes. The standard furnace has
baffles between the heat exchanger tubes as shown in 

FIGURE 48

.

(High CFM furnaces have only the top baffle support which does
not need to be removed for cleaning.) To remove the baffles, remove
the screws marked "A" in 

FIGURE 48,

 and slide each baffle forward.

Use a brush and/or an air hose to remove accumulated dust and
grease deposits from the tubes and the baffles. Re-install the baffles
by sliding them into the rear slot and replacing the screw.
The inner surfaces (combustion air side) of the heat exchanger can be
reached for cleaning with the burner rack removed. (See Paragraph

38.) An air hose; an 18-24" long, 1/2" diameter furnace brush (or heavy wire
with steel wool securely attached); a flashlight; and a mirror are needed.
The required procedure depends on the date of manufacture and whether or
not the furnace is rated for high (80%) efficiency. Furnaces designed to
provide high efficiency heating have "V" shaped baffles in the top of each
heat exchanger tube. Follow these instructions to remove these baffles
when cleaning the inner surfaces of the heat exchanger.

NOTE: 

High efficiency furnaces manufactured prior to 3/95 have a "C"

prefix in their model designation. All furnaces manufactured beginning 3/95
are designed for high efficiency and include these heat exchanger "V" baffles.

Instructions to Remove Heat Exchanger "V" Baffles:
Outdoor, Gravity Vent Model Series CRGB (See FIGURE 49)

1) Remove the ends of the flue gas collection box. On the control side of

the furnace, remove the block-off plate to gain access to the collection
box end.

2)

Sizes 75-175

 - Remove one of the tube baffle retaining angles on each

inside wall of the collection box. Each angle has one screw.

Sizes 200-400

 - Remove the flue diverter. Remove the screw at each

end and slide the flue diverter out of the furnace.

3) Pull the "V" baffles out of the heat exchanger.

Outdoor, Power Vent Model Series RPB

1) Remove the ends of the flue gas collection box. On the control side of

the furnace, remove the venter assembly and the flue outlet duct to
gain access to the collection box end.

2)

Sizes 125-300

 - Remove one of the tube baffle retaining angles on

each inside wall of the collection box. Each angle has one screw.

Size 400

 - Remove the inner baffle from the flue collection box. On

the control side, align the inner baffle with the slot in the collection
box edge. Pull the inner baffle until it clears the heat exchanger.
Remove the screw at each end and slide the flue diverter out of the
furnace.

3) Pull the "V" baffles out of the heat exchanger.

FIGURE 49 -
Remove
"V" Baffles to Clean Inner Surface of Heat Exchanger Tubes

Содержание CRGB Series

Страница 1: ...AquaSaver Timer Adjustment 34 Belts 24 Blocked Vent Switch 25 Blower Motors 24 Blower Rotation 24 Burner Air Adjustment 30 Burner Rack Removal 42 Burners 29 Carryover System 29 Check Installation and...

Страница 2: ...rhalogenatedhydrocarbonsorany contaminant silicone aluminium oxide etc that adheres to the spark ignition flame sensing probe b Wiring is not in accordance with the diagram furnished with the heater c...

Страница 3: ...x 19 1 2 495mm Return Air Openings with Optional Cabinet X Hanger Centerline Standard and Optional Blower Cabinet Dimensions inches andmm Gravity Vented Indoor Models XE HXE Gas Connection Natural Pr...

Страница 4: ...side the downturn plenum cabinet For dimensions with downturn plenum cabinet with a cooling coil cabinet see page 6 FIGURE1B Dimensions Outdoor Gravity VentedModel Series CRGB Vent Cap Gas Connection...

Страница 5: ...ottom of cabinet side If system has a cooling coil cabinet add length dimension on page 6 for full system length The two position discharge dampers in Option AQ8 fit in the discharge air opening The d...

Страница 6: ...ownturnPlenumCabinet factoryattachedto either type of Cooling Coil Cabinet Front View DX Coil Cabinet with Horizontal Discharge Option AU3 Liquid Line Connections 7 8 or 1 3 8 5 1 8 130 8 203 3 4 19 3...

Страница 7: ...r from inside the building openings 1 square inch free area per 1000 BTUH Never less than 100 square inches free area for each open ing See 1 in FIGURE 2 2 Air from outside through duct openings 1 squ...

Страница 8: ...the pipe hanger to a 1 threaded pipe See the suspension method on the left in FIGURE 4 As an alternative method the factory installed pipe hanger may be removed and the heater suspended as illustrated...

Страница 9: ...lled 1 Position curb cross rails and curb side rails as illustrated in FIGURE 8 page 10 If there are two side pieces to a side fasten them with splice plates and hardware as illustrated in the splicin...

Страница 10: ...e is horizontal If the system has an AU11 AU12 AU13 AU14 cooling coil cabinet there is a downturn plenum with vertical discharge Options AU2 AU3 AU11 AU12 AU13 and AU14 are not factory installed Optio...

Страница 11: ...should be supported every six feet 1 8M using a non combustible material such as strap steel or chain Do not rely on the drafthood or heater for support of either horizontal or vertical vent pipe 6 V...

Страница 12: ...re horizontal venting is required or where negative building pressure inhibits gravity venting in stall an optional power venter Option CA Use only a power venter provided by the furnace manufacturer...

Страница 13: ...mmended size is 1 2 x1 2 20 gauge FIGURE11B InstallationoftheVentCap includedinthe optionpackage andthefield suppliedPipingandSupports Oval Adapter Assy PN 103025 Venter Seal Plate P N 43446 9 Condens...

Страница 14: ...air duct should come in con tact with masonry walls Insulate around all air duct through ma sonry walls with not less than 1 2 1 is recommended of insula tion Through Unheated Space Insulate all expo...

Страница 15: ...l connections are made disconnect the pilot supply at the control valve and bleed the system of air Reconnect the pilot line and leak test all connections by brushing on a soap solution WARNING All co...

Страница 16: ...ding MUST be made in accordance with the National Electric CodeANSI NFPANo 70 latest edition or in Canada the Canadian Electrical Code Part I C S A Standard C22 1 In addition the installer should be a...

Страница 17: ...ontrols available as part of the gas and air control options Check the wiring diagram and literature supplied with the unit for operation of factory installed optional controls See FIGURE 19 for locat...

Страница 18: ...ND BLOWER MOTOR BRANCH CIRCUIT WIRE SHOULD BE SIZED TO TEMPERATURE RATING OF AT LEAST 105 C EXCEPT FOR MUST BE REPLACED IT MUST BE REPLACED WITH WIRING MATERIAL HAVING A 4 CAUTION IF ANY OF THE ORIGIN...

Страница 19: ...W LEADS CAP RED 8 USE 18 GA WIRE FOR 24 VOLT CONTROL WIRING ON UNIT NONE NOTES 4 CAUTION IF ANY OF THE ORIGINAL WIRE AS SUPPLIED WITH THE APPLIANCE MUST BE REPLACED IT MUST BE REPLACED WITH WIRING MAT...

Страница 20: ...L WIRE AS SUPPLIED WITH THE APPLIANCE 3 DOTTED WIRING AND THE FOLLOWING CONTROLS ARE SUPPLIED AND INSTALLED 2 THE FOLLOWING CONTROLS ARE SUPPLIED AS OPTIONAL EQUIPMENT 1 THE FOLLOWING CONTROLS ARE SUP...

Страница 21: ...N IF ANY OF THE ORIGINAL WIRE AS SUPPLIED WITH THE APPLIANCE 3 DOTTED WIRING AND THE FOLLOWING CONTROLS ARE SUPPLIED AND INSTALLED 2 THE FOLLOWING CONTROLS ARE SUPPLIED AS OPTIONAL EQUIPMENT 1 THE FOL...

Страница 22: ...E SAFETY SWITCH PORTION OF THE CONTROL THE SWITCH ACTION PROVES THE PRESENCE OF THE PILOT FLAME AND ENERGIZED THE A PILOT FLAME ON EACH OPERATING CYCLE THE SENSING PROBE ENERGIZING THE PILOT GAS VALVE...

Страница 23: ...ND ENERGIZES THE MAIN VALVE THE MAIN GAS IGNITES AND THE UNIT FIRES AT LOW RATE 3 ON A CALL FOR HEAT BY THE HIGH STAGE OF THERMOSTAT THE UNIT FIRES AT FULL RATE 4 IF THE FLAME IS EXTINGUISHED DURING M...

Страница 24: ...outlet temperature turn the adjustable half of the pulley outward One turn of the pulley will change the speed 8 10 5 Tighten the setscrew on the flat portion of the pulley shaft 6 Replace the belt an...

Страница 25: ...ing pressure levels off If a restriction or excessive flue length or turns cause the sensing pres sure to become less than the switch setpoint the pressure switch will function to shut off the main bu...

Страница 26: ...e same as the one illustrated 1 Remove the access panel in the ductwork adjacent to the control compartment access panel 2 Element is retained by spring clips 3 Round gasket and metal retaining plate...

Страница 27: ...IGURE24 Signal Conditioner used in Options AG21 and AG40 Carryover Regulator Modulating Valve Single Stage Gas PrimaryGas FlowPressure Switch WhiteLabel 1 1 w c GasFlow PressureSwitch WhiteLabel 1 1 w...

Страница 28: ...per open Is there voltage between Terminal 88 and Terminal 7 Is there voltage between Terminal 4 on ignition permissive relay and Terminal 7 Replace 1 time delay relay Replace ignition permissive rela...

Страница 29: ...6 38mm 79 23 32 18 25mm 7 16 1 16 11mm 1 6 Option AH2 and spark pilot with lockout is Option AH3 NOTE Outdoor units in Canada using propane require lockout Indoor units in U S and Canada using propane...

Страница 30: ...ers cont d INDOOR Gravity Vented Furnace Models XE HXE Natural gas burners are equipped with two flash carryover systems that receive a supply of gas simultaneously with the main burner NOTE A natural...

Страница 31: ...esuppliedwithairforcombustionasrequired by Code and in Paragraph 6A of this heater installation manual MAINTAIN THE VENT SYSTEM IN STRUCTURALLY SOUND AND PROPERLYOPERATINGCONDITION lockout control if...

Страница 32: ...3 Bottom Panel Position the air hood bottom panel so that it is to the inside of the two side panels and above the factory installed support angle Attach to the side panels If the bottom panel does n...

Страница 33: ...ecessary Follow these instructions to field connect the water supply and make neces sary checks and adjustments before operating the cooling module with a lock nut and a sealing gasket Check these fit...

Страница 34: ...ockwise to increase the ON time or counterclockwise to decrease the ON time One complete turn will adjust the cycle by 12 to 14 seconds All Modules Check the reservoir for any water leaks The reservoi...

Страница 35: ...e the water feed line from the downstream side of the ball valve and unscrew the water bleed line barbed hose fitting 3 Force a fresh water supply through the water inlet hose and thoroughly flush the...

Страница 36: ...let DamperOptionsonIndoor ModelsXE HXE FIGURE 41B Location of Controls for30 OutsideAirHood andDamperOptions AR6orAR7 OutdoorModelsonly FIGURE41D Exampleof OutsideAirand Return Air Damper Linkage Damp...

Страница 37: ...w c Heater Filter Size Metal Fillers Size A B C D E F1 F2 75 100 125 20x20 20x20 150 175 20x25 20x25 13 16 13 16 200 225 16x25 16x20 16x25 16x20 250 300 20x25 20x20 20x25 20x20 350 20x25 20x25 20x25...

Страница 38: ...B D D E 25 635mm 20 508mm 20 508mm 25 635mm Size 350 D D D C C Size 400 25 635mm 20 508mm B D Key Filter Code Filter Size A 16 x 20 B 20 x 20 C 16 x 25 D 20 x 25 E 25 x 25 Shaded areas are filter blo...

Страница 39: ...d with op tional discharge dampers the damper motor wires must be connected to the terminal blocks in the furnace electrical compartment If the coil cabinet being installed does not include a downturn...

Страница 40: ...ection remove the center hole plug FIGURE 46H To install side and top fillerpanels remove screws from top corners of both cabinets and the entire row across the cooling coil cabinet Removerowofscrews...

Страница 41: ...or lint accumulation Clean as needed Check the vent system for soundness Replace any parts that do not appear sound Check the wiring for any damaged wire Replace damaged wiring See Paragraph 12 for re...

Страница 42: ...ryover systems with air pressure 40 Cleaning the Heat Exchanger To clean the outer surfaces circulating air side of the heat exchanger gain access by removing the inspection panels in the ductwork or...

Страница 43: ...causes 8 Reset lockout by interrupting control at thermostat 9 Faulty combustion air proving switch 9 Replace combustion air proving switch 10 Activated blocked vent switch indoor system 10 Correct ve...

Страница 44: ...AG39 or AG40 see page 28 For replacement parts refer to Form P X XE for indoor units or Form P RG RP RBL for outdoor units Problem Probable Cause Remedy Pump does not run Unit is 1 Electrical connecti...

Отзывы: