background image

Form I-XE/CRGB/RPB, Page 12

Top

Bottom

12”

(305mm)

2” (51mm)

3/8”

(10mm)

Vent Cap

Vent Opening

Furnace Top

Vent Cap

Extension

Control Compartment

Access Panel

FIGURE 9B - Vent
Cap Installation

FIGURE 9A - Vent Cap
Extension, P/N 20524

8B. Venting - Gravity-Vented, Outdoor Model

Series CRGB

The appropriate size of gravity vent cap is supplied with the furnace. 

The

gravity vent cap requires field installation.

WARNING: This gravity-vented furnace should be
located on a roof or slab with at least 30-foot (9M)
radius between the center of the vent cap and
obstructions such as walls, parapets or cupolas. See
Hazard Levels, page 2.

8A. Gravity-Vented Models XE/HXE (cont'd)

Venting Requirements - Indoor Models (cont'd)

(b) 

Use double-wall, Type B vent pipe which is recommended for the

reduction or elimination of condensate problems. Where extreme condi-
tions are present and condensate is anticipated, install a trap for collect-
ing condensate.

8.

The vent connection may be made into a suitable permanent chimney
or into a gas vent. The effective area of the vent con-nector, gas vent, or
chimney when connected to a single appliance shall not be less than the
area of the appliance drafthood outlet or in accordance with approved
venting methods. The effective area of the gas vent or chimney when
connected to more than one appliance shall not be less than the area of
the largest vent connector plus 50% of the areas of additional vent
connectors or in accordance with approved venting methods.

Minimum permissible height of the vertical vent is five feet (1.5M)

providing no horizontal vent pipe connector is used. If a horizontal
vent connector is necessary, consult 

TABLES 1 or 2 

or the National

Fuel Gas Code or the Canadian Installation Code for Gas Burning
Appliances, for the maximum permissible length of a horizontal pipe
run (vent connector) for a given vertical height of gas vent.

The gas vent or chimney should extend at least three feet (.9M) above

the highest point where it passes through a roof of a building and at
least two feet (.6M) higher than any portion of a building or obstruc-
tion within a horizontal distance of ten feet (3M). A suitable weather
cap should be installed on the end of the vent pipe to prevent rain or
snow from entering the open end.

9.

If the heater is installed in a space served by a large exhaust fan, be sure
that the exhaust fan does not affect the operation of the heater or the
satisfactory venting of its products of combustion.

 

If a negative pressure exists, as evidenced by a downdraft, a factory-

designed mechanical motor driven venter (Option CA) should be in-
stalled. In severe negative pressure conditions, makeup air equipment
may be necessary.

Optional Power Venting (Option CA)

To install a gravity-vented furnace in an area where horizontal venting is
required or where negative building pressure inhibits gravity venting, in-
stall an optional power venter (Option CA). Use only a power venter
provided by the furnace manufacturer and carefully follow the instruc-
tions included in the optional venter package. Use the venter adapter
supplied to connect the power venter to the heater. 

Do not install the

power venter without the venter adapter.

With an Option CA power venter installed, the furnace may be vented
either horizontally or vertically. Do not exceed the maximum vent lengths
shown in the table below. Minimum vent length is 5 ft (1.5M).

Vent Cap Installation Instructions:

IMPORTANT REQUIREMENT

For proper operation of the gravity vent cap, position the
holes so that the solid side panel of the cap will face the
control compartment access panel side of the furnace. See
FIGURE 9B.

1) Furnaces that do not require a Vent Cap Extension
(H)CRGB Sizes 75- 300, 

align holes and attach the vent cap to the

furnace flue collar with sheetmetal screws. 

(See Important Require-

ment above.)

2) Furnaces that require a Vent Cap Extension (packed inside
the vent cap) - See FIGURES 9A and 9B
(H)CRGB Sizes 350 and 400

 require a 12" extension to raise the

vent cap above the top of the furnace.

a) Remove the extension from the inside of the cap.
b) Attach the extension to the furnace flue collar --

1) With 3/8" centerline clearance holes at the bottom, wrap

extension 

around

 flue collar on the top of the furnace.

2) Align holes in the extension with holes in the flue collar.
3) Secure with #10 1/2" sheetmetal screws.

c) Attach the vent cap to

the extension --

1) Position vent cap 

into

top of extension.

(See Important
Requirement
above)

2) Align holes and push

cap into extension.

3) Secure with 1/2"

sheetmetal screws.

Optional 4-foot (1.2M) Stack Extension for
Outdoor, Gravity Vent Models (Option ZZ)

Outdoor, gravity-vented furnaces that are factory-built with Option
ZZ are designed to release flue gases four feet (1.2M) above the top
of the furnace. A field-provided 4-ft (1.2M) vent extension must be
installed between the top of the furnace and the bottom of the vent
cap. (See 

FIGURE 9C

). Furnaces with Option ZZ (factory-installed

restrictor plus field-provided 4-ft stack) may be installed adjacent to
fresh air inlet(s) when local code requires that release of flue gases be
above an adjacent fresh air inlet that is not part of the furnace.

75, 100, 125, 150 175

200

225

250

300

350

400

ft

100

75

50

35

30

15

M

30

23

15

11

9

4.6

ft

100** 100** 100

92

M

30**

30**

30

4"

6"

Maximum* Vent Length (ft or M) for Furnace with Optional 

Power Venter (Option CA)

Vent Pipe 

Diameter

*

 Reduce the vent pipe lengths as follows for each item: 45° Elbow - 7ft

(2.1M); 90° Elbow - 15ft (4.6M); Reznor

®

 or Breidert Vent Cap - 10ft (3M).

**

 If the venter outlet is 4", connect a taper-type "enlarger" to the vent

outlet when installing 6" vent pipe.

Model

 Size 

Vent Cap 

Size

Extension Required

75, 100

6"

125, 175

8"

No

225, 250, 300

10"

350, 400

12"

Yes (packed inside cap)

(H)CRGB

Содержание CRGB Series

Страница 1: ...AquaSaver Timer Adjustment 34 Belts 24 Blocked Vent Switch 25 Blower Motors 24 Blower Rotation 24 Burner Air Adjustment 30 Burner Rack Removal 42 Burners 29 Carryover System 29 Check Installation and...

Страница 2: ...rhalogenatedhydrocarbonsorany contaminant silicone aluminium oxide etc that adheres to the spark ignition flame sensing probe b Wiring is not in accordance with the diagram furnished with the heater c...

Страница 3: ...x 19 1 2 495mm Return Air Openings with Optional Cabinet X Hanger Centerline Standard and Optional Blower Cabinet Dimensions inches andmm Gravity Vented Indoor Models XE HXE Gas Connection Natural Pr...

Страница 4: ...side the downturn plenum cabinet For dimensions with downturn plenum cabinet with a cooling coil cabinet see page 6 FIGURE1B Dimensions Outdoor Gravity VentedModel Series CRGB Vent Cap Gas Connection...

Страница 5: ...ottom of cabinet side If system has a cooling coil cabinet add length dimension on page 6 for full system length The two position discharge dampers in Option AQ8 fit in the discharge air opening The d...

Страница 6: ...ownturnPlenumCabinet factoryattachedto either type of Cooling Coil Cabinet Front View DX Coil Cabinet with Horizontal Discharge Option AU3 Liquid Line Connections 7 8 or 1 3 8 5 1 8 130 8 203 3 4 19 3...

Страница 7: ...r from inside the building openings 1 square inch free area per 1000 BTUH Never less than 100 square inches free area for each open ing See 1 in FIGURE 2 2 Air from outside through duct openings 1 squ...

Страница 8: ...the pipe hanger to a 1 threaded pipe See the suspension method on the left in FIGURE 4 As an alternative method the factory installed pipe hanger may be removed and the heater suspended as illustrated...

Страница 9: ...lled 1 Position curb cross rails and curb side rails as illustrated in FIGURE 8 page 10 If there are two side pieces to a side fasten them with splice plates and hardware as illustrated in the splicin...

Страница 10: ...e is horizontal If the system has an AU11 AU12 AU13 AU14 cooling coil cabinet there is a downturn plenum with vertical discharge Options AU2 AU3 AU11 AU12 AU13 and AU14 are not factory installed Optio...

Страница 11: ...should be supported every six feet 1 8M using a non combustible material such as strap steel or chain Do not rely on the drafthood or heater for support of either horizontal or vertical vent pipe 6 V...

Страница 12: ...re horizontal venting is required or where negative building pressure inhibits gravity venting in stall an optional power venter Option CA Use only a power venter provided by the furnace manufacturer...

Страница 13: ...mmended size is 1 2 x1 2 20 gauge FIGURE11B InstallationoftheVentCap includedinthe optionpackage andthefield suppliedPipingandSupports Oval Adapter Assy PN 103025 Venter Seal Plate P N 43446 9 Condens...

Страница 14: ...air duct should come in con tact with masonry walls Insulate around all air duct through ma sonry walls with not less than 1 2 1 is recommended of insula tion Through Unheated Space Insulate all expo...

Страница 15: ...l connections are made disconnect the pilot supply at the control valve and bleed the system of air Reconnect the pilot line and leak test all connections by brushing on a soap solution WARNING All co...

Страница 16: ...ding MUST be made in accordance with the National Electric CodeANSI NFPANo 70 latest edition or in Canada the Canadian Electrical Code Part I C S A Standard C22 1 In addition the installer should be a...

Страница 17: ...ontrols available as part of the gas and air control options Check the wiring diagram and literature supplied with the unit for operation of factory installed optional controls See FIGURE 19 for locat...

Страница 18: ...ND BLOWER MOTOR BRANCH CIRCUIT WIRE SHOULD BE SIZED TO TEMPERATURE RATING OF AT LEAST 105 C EXCEPT FOR MUST BE REPLACED IT MUST BE REPLACED WITH WIRING MATERIAL HAVING A 4 CAUTION IF ANY OF THE ORIGIN...

Страница 19: ...W LEADS CAP RED 8 USE 18 GA WIRE FOR 24 VOLT CONTROL WIRING ON UNIT NONE NOTES 4 CAUTION IF ANY OF THE ORIGINAL WIRE AS SUPPLIED WITH THE APPLIANCE MUST BE REPLACED IT MUST BE REPLACED WITH WIRING MAT...

Страница 20: ...L WIRE AS SUPPLIED WITH THE APPLIANCE 3 DOTTED WIRING AND THE FOLLOWING CONTROLS ARE SUPPLIED AND INSTALLED 2 THE FOLLOWING CONTROLS ARE SUPPLIED AS OPTIONAL EQUIPMENT 1 THE FOLLOWING CONTROLS ARE SUP...

Страница 21: ...N IF ANY OF THE ORIGINAL WIRE AS SUPPLIED WITH THE APPLIANCE 3 DOTTED WIRING AND THE FOLLOWING CONTROLS ARE SUPPLIED AND INSTALLED 2 THE FOLLOWING CONTROLS ARE SUPPLIED AS OPTIONAL EQUIPMENT 1 THE FOL...

Страница 22: ...E SAFETY SWITCH PORTION OF THE CONTROL THE SWITCH ACTION PROVES THE PRESENCE OF THE PILOT FLAME AND ENERGIZED THE A PILOT FLAME ON EACH OPERATING CYCLE THE SENSING PROBE ENERGIZING THE PILOT GAS VALVE...

Страница 23: ...ND ENERGIZES THE MAIN VALVE THE MAIN GAS IGNITES AND THE UNIT FIRES AT LOW RATE 3 ON A CALL FOR HEAT BY THE HIGH STAGE OF THERMOSTAT THE UNIT FIRES AT FULL RATE 4 IF THE FLAME IS EXTINGUISHED DURING M...

Страница 24: ...outlet temperature turn the adjustable half of the pulley outward One turn of the pulley will change the speed 8 10 5 Tighten the setscrew on the flat portion of the pulley shaft 6 Replace the belt an...

Страница 25: ...ing pressure levels off If a restriction or excessive flue length or turns cause the sensing pres sure to become less than the switch setpoint the pressure switch will function to shut off the main bu...

Страница 26: ...e same as the one illustrated 1 Remove the access panel in the ductwork adjacent to the control compartment access panel 2 Element is retained by spring clips 3 Round gasket and metal retaining plate...

Страница 27: ...IGURE24 Signal Conditioner used in Options AG21 and AG40 Carryover Regulator Modulating Valve Single Stage Gas PrimaryGas FlowPressure Switch WhiteLabel 1 1 w c GasFlow PressureSwitch WhiteLabel 1 1 w...

Страница 28: ...per open Is there voltage between Terminal 88 and Terminal 7 Is there voltage between Terminal 4 on ignition permissive relay and Terminal 7 Replace 1 time delay relay Replace ignition permissive rela...

Страница 29: ...6 38mm 79 23 32 18 25mm 7 16 1 16 11mm 1 6 Option AH2 and spark pilot with lockout is Option AH3 NOTE Outdoor units in Canada using propane require lockout Indoor units in U S and Canada using propane...

Страница 30: ...ers cont d INDOOR Gravity Vented Furnace Models XE HXE Natural gas burners are equipped with two flash carryover systems that receive a supply of gas simultaneously with the main burner NOTE A natural...

Страница 31: ...esuppliedwithairforcombustionasrequired by Code and in Paragraph 6A of this heater installation manual MAINTAIN THE VENT SYSTEM IN STRUCTURALLY SOUND AND PROPERLYOPERATINGCONDITION lockout control if...

Страница 32: ...3 Bottom Panel Position the air hood bottom panel so that it is to the inside of the two side panels and above the factory installed support angle Attach to the side panels If the bottom panel does n...

Страница 33: ...ecessary Follow these instructions to field connect the water supply and make neces sary checks and adjustments before operating the cooling module with a lock nut and a sealing gasket Check these fit...

Страница 34: ...ockwise to increase the ON time or counterclockwise to decrease the ON time One complete turn will adjust the cycle by 12 to 14 seconds All Modules Check the reservoir for any water leaks The reservoi...

Страница 35: ...e the water feed line from the downstream side of the ball valve and unscrew the water bleed line barbed hose fitting 3 Force a fresh water supply through the water inlet hose and thoroughly flush the...

Страница 36: ...let DamperOptionsonIndoor ModelsXE HXE FIGURE 41B Location of Controls for30 OutsideAirHood andDamperOptions AR6orAR7 OutdoorModelsonly FIGURE41D Exampleof OutsideAirand Return Air Damper Linkage Damp...

Страница 37: ...w c Heater Filter Size Metal Fillers Size A B C D E F1 F2 75 100 125 20x20 20x20 150 175 20x25 20x25 13 16 13 16 200 225 16x25 16x20 16x25 16x20 250 300 20x25 20x20 20x25 20x20 350 20x25 20x25 20x25...

Страница 38: ...B D D E 25 635mm 20 508mm 20 508mm 25 635mm Size 350 D D D C C Size 400 25 635mm 20 508mm B D Key Filter Code Filter Size A 16 x 20 B 20 x 20 C 16 x 25 D 20 x 25 E 25 x 25 Shaded areas are filter blo...

Страница 39: ...d with op tional discharge dampers the damper motor wires must be connected to the terminal blocks in the furnace electrical compartment If the coil cabinet being installed does not include a downturn...

Страница 40: ...ection remove the center hole plug FIGURE 46H To install side and top fillerpanels remove screws from top corners of both cabinets and the entire row across the cooling coil cabinet Removerowofscrews...

Страница 41: ...or lint accumulation Clean as needed Check the vent system for soundness Replace any parts that do not appear sound Check the wiring for any damaged wire Replace damaged wiring See Paragraph 12 for re...

Страница 42: ...ryover systems with air pressure 40 Cleaning the Heat Exchanger To clean the outer surfaces circulating air side of the heat exchanger gain access by removing the inspection panels in the ductwork or...

Страница 43: ...causes 8 Reset lockout by interrupting control at thermostat 9 Faulty combustion air proving switch 9 Replace combustion air proving switch 10 Activated blocked vent switch indoor system 10 Correct ve...

Страница 44: ...AG39 or AG40 see page 28 For replacement parts refer to Form P X XE for indoor units or Form P RG RP RBL for outdoor units Problem Probable Cause Remedy Pump does not run Unit is 1 Electrical connecti...

Отзывы: