6

OPT-AS3,4,5,8 (07-22) 160202-B

INSTALLATION—CONTINUED

Installation/Replacement of Media Pads

NOTE:  Option ASA1 moisture elimination pads are shipped separately for field-installation.

Install/replace media pads and/or moisture elimination pads as follows:
1.  Remove media pads (see 

Figure 5

):

a.  Remove three screws that secure top pad retainer and release top pad retainer from cooling module.
b.  Remove three screws that secure bottom pad retainer and release bottom pad retainer from cooling module.
c.  Disengage screen retainers from sides of media pads.
d.  Disengage inlet screen from media pads and remove media pads from cooling module.
e.  Slide all media pads horizontally away from cooling module until clear of bottom reservoir pan.

Figure 5.  Media Pad Assembly

2.  Install moisture elimination pads if required (see 

Figure 6

):

a.  Install two catch pad clamps to one side of cooling module’s front legs and secure clamps through legs into 

clamp using four screws (8).

b.  Assemble catch pads together using three screws (8).

NOTE:  The screen part of the catch pad assembly should always be facing the attached air mover.

c.  Guide catch pad assembly through inlet of cooling module and place bottom of lower pad into catch pad mounting 

trough (see 

Figure 4

). Slide catch pad assembly into two slots located in catch pad clamps installed in step 2a.

d.  With pads in place, slide one of two remaining clamps over middle seam where assembled catch pads meet. 

Slide other clamp over top catch pad frame and secure both clamps to cooling module leg using screws (8).

⚠ CAUTION ⚠

IMPORTANT: Cooling media is made up of two different sheets of cooling material, each with 

its own unique angle. When replacing the cooing media, BE CERTAIN that the 45° angle slopes 

downward toward the incoming outside air. If the media is not installed properly, water blowoff 

from the media pads will occur.

Содержание AS3

Страница 1: ...ling modules require outside air TABLE OF CONTENTS GENERAL INFORMATION 1 Dimensions 2 Weights 2 INSTALLATION 3 Pre Installation Checklist 3 Assemble Base 3 Install Evaporative Cooling Module on Base 4...

Страница 2: ...1 Evaporative Cooling Module Installation Components Item No Component PN Quantity Application 1 End rail 107235 2 Base assembly 2 Side rail 107227 2 3 Two piece leg 107236 4 4 Front top cover 107228...

Страница 3: ...drain and fill kit freeze protection kit moisture elimination pads and or water hammer arrestor check to ensure that these parts are available for installation Ensure that there is adequate clearance...

Страница 4: ...odule with both ends supported and place it on base assembly Ensure that module is level and that all base assembly bolts are secure 2 Install top front cover 4 and secure using 13 screws 8 three per...

Страница 5: ...oling module using screws 8 five per side 4 Secure transition duct flange to front top cover 4 using seven screws 8 5 With cooling module and transition duct properly positioned on blower cabinet tigh...

Страница 6: ...ure 6 a Install two catch pad clamps to one side of cooling module s front legs and secure clamps through legs into clamp using four screws 8 b Assemble catch pads together using three screws 8 NOTE T...

Страница 7: ...rection Through Media Pads Pump Junction Box Assembly Installation NOTE To avoid damage during shipping the pump junction box assembly is secured to the top of the side panel 1 Support pump junction b...

Страница 8: ...mp Junction Box Assembly Electrical Connections PUMP JUNCTION BOX ASSEMBLY OPERATING LOCATION Figure 9 Evaporative Cooling Module Factory Installed Wiring BL MODELS WITH 115 230 1 60 OR 230 460 575 3...

Страница 9: ...interfere with damper controls 5 Run wires up to electrical compartment remove plug from one bottom entrance hole and push tubing encased wires into electrical compartment Place other strain relief bu...

Страница 10: ...iddle outlet to supply water to cooling module reservoir b For drain two way valve connections connect drain pipe from reservoir to A and connect outlet side to B and connect into drain lines from coo...

Страница 11: ...dule All cooling modules are equipped with an overflow and drain fitting The fittings are in the cabinet bottom and come complete with a locknut and a sealing gasket Check these fittings for tightness...

Страница 12: ...ailure to do so can cause electrical shock personal injury or death CAUTION Do not flood the media pads with extreme quantities of water for long periods as this will cause premature breakdown of the...

Страница 13: ...iven temperature the media pads should completely wet from top to bottom dur ing the ON cycle The AquaSaver microprocessor has three preset timing settings based on media size The appropriate setting...

Страница 14: ...on Remove the water feed line from the downstream side of the ball valve and unscrew the water bleed line barbed hose fitting Force a fresh water supply up through the water inlet hose and thoroughly...

Страница 15: ...ow section 2 Dirty media pads Clean or replace media pads refer to Installation Replacement of Media Pads section D Water not distributing evenly 1 Distribution line clogged Flush distribution line re...