Configuration of Pressure Sensor
For application using Rexroth HM20 pressure transducer, configuration pa‐
rameters of HM20 sensor can be automatically loaded by selecting the corre‐
sponding type code in parameter F2.10. Please make sure the right analog
input channel has been set through [F2.00]...[F2.02] before setting [F2.10],
since the configuration parameters (AI input mode and scaling factors) will be
set for the selected channel for pressure feedback.
The pressure feedback is required to observe the hydraulic load and to trig‐
ger the automatic boost function. Therefore, analog input AI2 has to be con‐
figured with respect to the installed pressure transducer.
Code
Name
Setting range
Default
Attri.
E1.35
AI1 input mode
0: 0...20 mA
1: 4...20 mA
2: 0...10 V
3: 0...5 V
4: 2…10 V
2
Run
E1.40
AI2 input mode
1
Run
H8.05
EAI input mode
0...4 (same as E1.35)
5: -10...10 V
0
Stop
F2.00
Analog input AI1
0: No function assigned
1: Pressure command
2: Pressure feedback
3: Oil level warning / error
4: Oil temperature
0
Stop
F2.02
Extended analog input EAI
0
Stop
F2.01
Analog input AI2
0: No function assigned
1: Pressure command
2: Pressure feedback
2
Stop
F2.04
Pressure command corresponding
to 10 V / 20 mA
0.1...1,000.0 bar
100.0
Stop
F2.05
Pressure command null offset in V
or mA
0...5.0 V, mA
0.1
Stop
F2.06
Pressure feedback corresponding
to 10V or 20mA
0.1...1,000.0 bar
100.0
Stop
Bosch Rexroth AG
DOK-SYTROX-DRN5020****-IT05-EN-P
84/143
Frequency-Controlled Pump Drive System Sytronix DRn 5020
Commissioning of Sytronix DRn 5020 System