10.8 Electrical Wiring
10.8.1 Wiring
Wiring 230 V
PE
PE
PE
PE
PE
PE
6 mm² (green/yellow)
16 mm² (green/yellow)
Min. 16 mm² (green/yellow)
To the housing of the control cabinet
PE neutral point
230V
400V
4 mm² (green/yellow)
16 mm² (green/yellow)
4 mm² (green/yellow)
Fuses, better: protective motor switches
W1
N
V1
U1
L1 L2 L3 N
Leads
L1.1
L2.1 L3.1 N
PE
PE
N
U2
PE
1
PE
N1 U2
4 mm² (green/yellow)
Length max. 4 m
Power supply unit
VAP01.1H-W23
024-010-NN
+24 V
0 V
DC 24 V
Overvoltage
category I
Overvoltage
category III
Overvoltage
category II
To the device
All housing parts (functional earth)
Terminals in
isolated
arrangement
e.g. drives
230 V power supply
operator terminals
service plug receptacle(s)
Transformer
acc. to EN 60742
N conductor:
Use only with
permission of
the operator!
Fig. 10-20: Wiring 230 V
High electrical voltage! Danger to life and risk of
injury caused by electric shock or bodily harm
caused by supply voltage on the protective ex-
tra-low voltage (e.g. +24 V)!
DANGER
Power supply units, whose net connection is designed for overvoltage category
II, are to be connected to a net voltage with overvoltage category II (see
10-20 "Wiring 230 V" on page 30
Bosch Rexroth AG
Assembly, Disassembly and Electrical Installation
VDP 16.3, VDP 40.3, VDP 60.3
30/53
DOK-SUPPL*-VDP*XX.3***-IT03-EN-P
Содержание IndraControl VDP 16.3
Страница 6: ...Bosch Rexroth AG VDP 16 3 VDP 40 3 VDP 60 3 IV DOK SUPPL VDP XX 3 IT03 EN P ...
Страница 57: ...VDP 16 3 VDP 40 3 VDP 60 3 Bosch Rexroth AG DOK SUPPL VDP XX 3 IT03 EN P 51 53 ...
Страница 58: ...Bosch Rexroth AG VDP 16 3 VDP 40 3 VDP 60 3 52 53 DOK SUPPL VDP XX 3 IT03 EN P ...
Страница 59: ...Notes VDP 16 3 VDP 40 3 VDP 60 3 Bosch Rexroth AG ...