Designation at
the housing
Connection type
Connector type, integra-
ted
Mating connector or ca-
ble (from outside)
XUSBIN
USB2.0 connection to the control
cabinet PC. Length 5 m max.
Use only a high-speed USB2.0 ca-
Accessories and Wear Parts" on
)
USB female connector,
Type B
USB connector,
Type B
Functional earth ground (FE)
M5
Ring cable lug
Tab. 9-1: Interfaces
Malfunctions due to insufficient shielding!
NOTICE
Use only shielded cables and metallic or conductive connector/coupling covers
with large-area shield support.
9.3 DC 24 V Voltage Supply
Fig. 9-2: Interface for 24 V voltage supply
Pin
Function
1
Supply v24 V
2
Supply voltage 0 V
3
n. c.
Use a 24 V industrial power supply unit acc. to DIN EN 60742, classification VDE
0551, for example "VAP01.1H-W23-024-010-NN" (parts number R911171065) for
the voltage supply.
For wiring connection terminals use copper wire only.
Bosch Rexroth AG
Interfaces
VDP 16.3, VDP 40.3, VDP 60.3
14/53
DOK-SUPPL*-VDP*XX.3***-IT03-EN-P
Содержание IndraControl VDP 16.3