Secure built-in devices from penetrating foreign objects and water, as
well as from direct contact, by providing an external housing, for exam‐
ple a control cabinet.
High housing voltage and high leakage current! Danger to life, risk of injury
by electric shock!
●
Before switching on and before commissioning, ground or connect the
components of the electric drive and control system to the equipment
grounding conductor at the grounding points.
●
Connect the equipment grounding conductor of the components of the
electric drive and control system permanently to the main power supply
at all times. The leakage current is greater than 3.5 mA.
●
Establish an equipment grounding connection with a minimum cross
section according to the table below. With an outer conductor cross sec‐
tion smaller than 10 mm
2
(8 AWG), the alternative connection of two
equipment grounding conductors is allowed, each having the same
cross section as the outer conductors.
Cross section outer con‐
ductor
Minimum cross section equipment grounding conductor
Leakage current ≥ 3.5 mA
1 equipment grounding
conductor
2 equipment grounding
conductors
1,5 mm
2
(AWG 16)
10 mm
2
(AWG 8)
2 × 1,5 mm
2
(AWG 16)
2,5 mm
2
(AWG 14)
2 × 2,5 mm
2
(AWG 14)
4 mm
2
(AWG 12)
2 × 4 mm
2
(AWG 12)
6 mm
2
(AWG 10)
2 × 6 mm
2
(AWG 10)
10 mm
2
(AWG 8)
-
16 mm
2
(AWG 6)
16 mm
2
(AWG 6)
-
25 mm
2
(AWG 4)
-
35 mm
2
(AWG 2)
-
50 mm
2
(AWG 1/0)
25 mm
2
(AWG 4)
-
70 mm
2
(AWG 2/0)
35 mm
2
(AWG 2)
-
...
...
...
Tab.3-1:
Minimum Cross Section of the Equipment Grounding Connection
3.3.2
Protective Extra-Low Voltage as Protection Against Electric Shock
Protective extra-low voltage is used to allow connecting devices with basic in‐
sulation to extra-low voltage circuits.
On components of an electric drive and control system provided by Rexroth,
all connections and terminals with voltages between 5 and 50 volts are PELV
("Protective Extra-Low Voltage") systems. It is allowed to connect devices
equipped with basic insulation (such as programming devices, PCs, note‐
books, display units) to these connections.
DOK-GEAR**-GTE********-PR08-EN-P
Rexroth GTE Planetary Gearboxes
Bosch Rexroth AG
15/83
Safety Instructions for Electric Drives and Controls
Содержание GTE Series
Страница 6: ...Bosch Rexroth AG DOK GEAR GTE PR08 EN P Rexroth GTE Planetary Gearboxes IV 83 ...
Страница 26: ...Bosch Rexroth AG DOK GEAR GTE PR08 EN P Rexroth GTE Planetary Gearboxes 24 83 ...
Страница 32: ...Bosch Rexroth AG DOK GEAR GTE PR08 EN P Rexroth GTE Planetary Gearboxes 30 83 ...
Страница 58: ...Bosch Rexroth AG DOK GEAR GTE PR08 EN P Rexroth GTE Planetary Gearboxes 56 83 ...
Страница 68: ...Bosch Rexroth AG DOK GEAR GTE PR08 EN P Rexroth GTE Planetary Gearboxes 66 83 ...
Страница 78: ...Bosch Rexroth AG DOK GEAR GTE PR08 EN P Rexroth GTE Planetary Gearboxes 76 83 ...
Страница 82: ...Bosch Rexroth AG DOK GEAR GTE PR08 EN P Rexroth GTE Planetary Gearboxes 80 83 ...
Страница 85: ...Notes DOK GEAR GTE PR08 EN P Rexroth GTE Planetary Gearboxes Bosch Rexroth AG 83 83 ...