Notes on DC_IN terminal
Converter in running status: Converter stops with error 'UE-1' at AC power loss
Conditions
Description
DC_IN power is available
'UE-1' remains to be displayed on the panel
'Power loss restart' function does NOT work
Converter can NOT be started by any command source
Limited* Parameters can be viewed but can NOT be modified
DC_IN power is unavailable
Converter panel blackout after a short time
AC power resumes
Converter will remain in stop state, 'UE-1' can be reset
'Power loss restart' function works
Tab. 8-9: Power loss in running status
Converter in stopped status: 'p.OFF' will be displayed at AC power loss
Conditions
Description
DC_IN power is available
'p.OFF' remains to be displayed on the panel
Converter can NOT be started by any command source
Limited* Parameters can be viewed but can NOT be modified
DC_IN power is unavailable
Converter panel blackout after a short time
AC power resumes
Converter will remain in stop state, 'p.OFF' disappears automatically
Tab. 8-10: Power loss in stopped status
EFC x610 Series
Bosch Rexroth AG
Frequency Converter Wiring
DOK-RCON03-EFC-X610***-IT05-EN-P
61/389
Содержание EFC 3610 Series
Страница 18: ...Bosch Rexroth AG EFC x610 Series XVI DOK RCON03 EFC X610 IT05 EN P ...
Страница 332: ...Fig 15 15 0020 N 03_0025 N 03 Bosch Rexroth AG Accessories EFC x610 Series 300 389 DOK RCON03 EFC X610 IT05 EN P ...
Страница 333: ...Fig 15 16 0025 A 05 EFC x610 Series Bosch Rexroth AG Accessories DOK RCON03 EFC X610 IT05 EN P 301 389 ...
Страница 336: ...Fig 15 21 0250 N 05 Bosch Rexroth AG Accessories EFC x610 Series 304 389 DOK RCON03 EFC X610 IT05 EN P ...
Страница 421: ...Notes EFC x610 Series Bosch Rexroth AG ...