E8: Standard communication parameters
Code
Name
Setting range
Default
Min.
Attri.
Communication protocol
0: Modbus
1: Extension card
0
–
Stop
Communication error
detection time
0.0...60.0 s
(0.0: Inactive)
0.0
0.1
Stop
Communication error
protection mode
0: Freewheeling stop
1: Keep running
1
–
Stop
Communication process
data loss behavior
0: Decelerating stop
1: Freewheeling stop
2: Keep running
0
–
Stop
Modbus baud rate
0: 1,200 bps; 1: 2,400 bps
2: 4,800 bps; 3: 9,600 bps
4: 19,200 bps; 5: 38,400 bps
3
–
Stop
Modbus data format
0...3
0
–
Stop
Modbus local address
1...247
1
1
Stop
Modbus level / edge sen-
sitivity selection
0: Level sensitive
1: Edge sensitive
1
–
Stop
Setting range of E8.11:
0: N, 8, 1 (1 start bit, 8 data bits, 1 stop bit, no parity)
1: E, 8, 1 (1 start bit, 8 data bits, 1 stop bit, even parity)
2: O, 8, 1 (1 start bit, 8 data bits, 1 stop bit, odd parity)
3: N, 8, 2 (1 start bit, 8 data bits, 2 stop bits, no parity)
EFC x610 Series
Bosch Rexroth AG
Appendix
DOK-RCON03-EFC-X610***-IT05-EN-P
353/389
Содержание EFC 3610 Series
Страница 18: ...Bosch Rexroth AG EFC x610 Series XVI DOK RCON03 EFC X610 IT05 EN P ...
Страница 332: ...Fig 15 15 0020 N 03_0025 N 03 Bosch Rexroth AG Accessories EFC x610 Series 300 389 DOK RCON03 EFC X610 IT05 EN P ...
Страница 333: ...Fig 15 16 0025 A 05 EFC x610 Series Bosch Rexroth AG Accessories DOK RCON03 EFC X610 IT05 EN P 301 389 ...
Страница 336: ...Fig 15 21 0250 N 05 Bosch Rexroth AG Accessories EFC x610 Series 304 389 DOK RCON03 EFC X610 IT05 EN P ...
Страница 421: ...Notes EFC x610 Series Bosch Rexroth AG ...