12.8.5 Indication of Simple PLC Status
An indication signal is active via 'DO1 output' or 'Relay 1 output' when a simple
PLC cycle or stage is complete.
Define the output with respective indication signals as below:
Code
Name
Setting range
Default
Min.
Attri.
E2.01 DO1 output setting
7: Simple PLC stage com-
plete
8: Simple PLC cycle com-
plete
1
–
Stop
E2.15 Relay 1 output selection
1
–
Stop
H8.20 EDO output setting
1
–
Stop
H8.21 Extended relay output selection
1
–
Stop
H9.00 Extended relay 1 output selection
0
–
Stop
H9.01 Extended relay 2 output selection
0
–
Stop
H9.02 Extended relay 3 output selection
0
–
Stop
H9.03 Extended relay 4 output selection
0
–
Stop
●
7: Simple PLC stage complete
f
out
Output frequency
d
out
Digital output
t
Time
Fig. 12-43: Simple PLC stage complete
When a stage is complete, a pulse signal is active for the duration of 0.5 s.
Any stage with running time of 0.0 s will be skipped without pulse output.
– If the running time of one stage is so short that it finishes before the 'Sim-
ple PLC stage complete' signal of the previous stage is deactivated, the sig-
nal remains active and the pulse duration calculation is restarted.
– If the setting frequency of next stage is lower than that of the current
stage, the frequency converter decelerates to the next stage with the de-
celeration time of current stage.
Bosch Rexroth AG
Functions and Parameters
EFC x610 Series
184/389
DOK-RCON03-EFC-X610***-IT05-EN-P
Содержание EFC 3610 Series
Страница 18: ...Bosch Rexroth AG EFC x610 Series XVI DOK RCON03 EFC X610 IT05 EN P ...
Страница 332: ...Fig 15 15 0020 N 03_0025 N 03 Bosch Rexroth AG Accessories EFC x610 Series 300 389 DOK RCON03 EFC X610 IT05 EN P ...
Страница 333: ...Fig 15 16 0025 A 05 EFC x610 Series Bosch Rexroth AG Accessories DOK RCON03 EFC X610 IT05 EN P 301 389 ...
Страница 336: ...Fig 15 21 0250 N 05 Bosch Rexroth AG Accessories EFC x610 Series 304 389 DOK RCON03 EFC X610 IT05 EN P ...
Страница 421: ...Notes EFC x610 Series Bosch Rexroth AG ...