10 User code
The access to some adjustment values can be restricted via a user code (customer).
1. Installer 0262 (Factory setting)
All menus and adjustment values are shown and all values can be altered.
2. Customer 0000
The installer level is not shown, adjustment values can be changed partly.
For safety reasons, the user code should generally be set to the customer code
before the controller is handed to the customer!
Î
In order to restrict the access, enter 0000 in the menu item User code.
°C °F
Ω
Pt1000
°C °F
Ω
Pt1000
-10
14
961
55
131
1213
-5
23
980
60
140
1232
0
32
1000
65
149
1252
5
41
1019
70
158
1271
10
50
1039
75
167
1290
15
59
1058
80
176
1309
20
68
1078
85
185
1328
25
77
1097
90
194
1347
30
86
1117
95
203
1366
35
95
1136
100 212
1385
40 104
1155
105 221
1404
45 113
1175
110 230
1423
50 122
1194
115 239
1442
The Lightwheel
®
flashes red.
Sensor fault. An error code instead of a temperature
is shown on the sensor display channel.
Fuse
Short circuit or line break
Disconnected temperature sensors can be checked
with an ohmmeter. Please check if the resistance
values correspond with the table.
11 Troubleshooting
If a malfunction occurs, a message will appear on the display of the controller.
Содержание DeltaTherm HT