3.1.7 Heat quantity measurement
OHQM
: Heat quantity
measurement
Adjustment range: OFF...ON-
Factory setting: OFF
Heat quantity measurement is possible if a flowmeter is
used. For this purpose, the heat quantity measurement op-
tion
OHQM
has to be enabled.
The flow rate should be read from the flowmeter (l/min)
and has to be adjusted in the channel
FMAX
. Antifreeze
type and concentration of the heat transfer medium have
to be adjusted in the channels
MEDT
and
MED%
.
Antifreeze type:
0 : water
1 : propylene glycol
2 : ethylene glycol
3 : Tyfocor
®
LS / G-LS
FMAX:
Flow rate in l/min
Adjustment range 0...20,
in 0.1 steps
Factory setting: 6,0
kWh/MWh
:Heat quantity
kWh / MWh
Display channel
MEDT:
Antifreeze type
Adjustment range: 0...3
Factory setting: 1
MED%:
Antifreeze concen-
tration in (Vol-) %
When MEDT 0 or 3 is used,
the parameter MED% is
‚hidden‘.
Adjustment range: 20... 70
Factory setting: 45
The flow rate as well as the reference sensors S1 (flow) and
S4 (return) are used for calculating the heat quantity sup-
plied. It is shown in kWh in the channel
kWh
uand in MWh
in the channel
MWh
. The overall heat quantity results from
the sum of both values.
The accumulated operating hours can be set back to zero.
As soon as one of the display channels of the heat quantity
is selected, the symbol
is displayed. Press the SET (3)
button for approx. 2 seconds in order to access the RESET-
mode of the counter. The display symbol
will flash and
the heat quantity value will be set to 0. Confirm the reset
with the
button in order to finish the reset.
In order to interrupt the RESET process, no button should
be pressed for about 5 seconds. The display returns to the
display mode.