4.3 

Heat exchange control

 Use grounding terminals!

7

RO RC N N L

8 9 10 11

2

2

2

3

3

S2

S1

RO

When the temperature difference between sensor 1 
(store 1) and sensor 2 (store 2) exceeds the adjust-
ed value, the circulating pump will be activated. Heat 
will be transferred from store 1 into store 2. If the 
temperature difference falls by 1.6 K (non-adjustable 
hysteresis) below the adjusted temperature difference, 
the pump will be switched off.

S1  =  Sensor store 1
S2  =  Sensor store 2
RO  =  Circulating pump

4.2 

Heating circuit return preheating

 Use grounding terminals!

The controller calculates the temperature difference 
between collector sensor S1 and store sensor S2. If 
the difference is larger than or identical to the adjust-
ed switch-on value, the controller switches the 3-port 
valve. The heat of the store is used for increasing the 
return temperature of the heating circuit. If the tem-
perature difference falls by 1.6 K (non-adjustable hys-
teresis) below the adjusted temperature difference, the 
valve will be put into its initial position.

S1  =  Store sensor
S2  =  Heating circuit return sensor
RO  =  3-port valve

7

RO RC N N L

8 9 10 11

2

2

3

3

S1

RO

S2

Mains

Mains

ON

OFF

1

2

3

4

E

A

ON

OFF

1

2

3

4

ON

OFF

1

2

3

4

E

A

ON

OFF

1

2

3

4

Содержание DeltaSol AX HE

Страница 1: ...d this manual carefully to get the best performance from this unit Please keep this manual safe DeltaSol AX HE www resol com Manual en Differential temperature controller Manual for the specialised cr...

Страница 2: ...exclusively addressed to authorised skilled personnel Only qualified electricians should carry out electrical works Initial installation must be effected by the system owner or qualified personnel nam...

Страница 3: ...ntees a protection against dripping water 1 Overview 4 2 Installation 4 2 1 Mounting 4 2 2 Electrical connection 6 3 Operation and function 6 3 1 Flashing codes 6 3 2 DIP switches and potentiometres 6...

Страница 4: ...m temperature limitation Housing plastic PC ABS and PMMA Mounting wall mounting Indication Display 1 operating control LED Operation 3 potentiometres 4 DIP switches 1 jumper Protection type IP 20 DIN...

Страница 5: ...2 2 1 112mm 2 5 6 7 3 8 4 T4A fuse Mains connection Relay load Grounding terminal common terminal block Sensor 1 2 PWM output DIP switches Switch on temperature difference potentiometre Temperature li...

Страница 6: ...normally closed contact 9 neutral conductor N Grounding terminal common terminal block Speed control of a HE pump is possible via a PWM signal The pump has to be connected to the relay power supply as...

Страница 7: ...the manual mode is active the operating control lamp flashes red and green 3 4 Manual mode 3 5 Maximum temperature limitation With DIP switch 2 the temperature limitation can be activated as a maximum...

Страница 8: ...eresis below the adjusted temperature difference the pump will be switched off S1 Collector sensor S2 Store sensor RO Solar pump ON OFF 1 2 3 4 C Deactivated by default DIP switch in OFF position de f...

Страница 9: ...cuit return preheating Use grounding terminals The controller calculates the temperature difference between collector sensor S1 and store sensor S2 If the difference is larger than or identical to the...

Страница 10: ...nce falls by 1 6K non adjust able hysteresis below the adjusted temperature differ ence the pump will be switched off S1 Solid fuel boiler sensor S2 Store sensor RO Circulating pump 5 Accessories SP10...

Страница 11: ...nnected temperature sensors can be checked with an ohmmeter Please check if the resistance values correspond with the table C F Pt1000 C F Pt1000 10 14 961 55 131 1213 5 23 980 60 140 1232 0 32 1000 6...

Страница 12: ...r the completeness of the drawings and texts of this manual they only represent some examples They can only be used at your own risk No liability is assumed for incorrect incomplete or false informati...

Отзывы: