The DIP switches (A) can be used for activating (ON) or deactivating (OFF) the 
following functions:
•  Manual mode (DIP switch 1)
•  Maximum temperature limitation (DIP switch 2)
•  Antifreeze function (DIP switch 3)
•  Minimum temperature limitation (DIP switch 4)
With the potentiometre on the left-hand side (E), the switch-on temperature dif-
ference can be adjusted (in K).
With the potentiometre on the right-hand side (D), the minimum speed of the HE 
pump can be adjusted, see chap. 3.8 on page 8. 
With the lower potentiometre (C), the temperature for the maximum or minimum 
temperature limitation can be adjusted (in °C).
With the jumper (B), the PWM profile of the output signal (solar or heating) can 
be selected.

Note
Pump speed control is only possible if a HE pump with a PWM input is 
used. 

3.3 

Switch-on temperature difference

ON

OFF

1

2

3

4

E

The controller calculates the temperature difference 
between the temperature sensors S1 and S2. If the dif-
ference is larger than or identical to the switch-on val-
ue adjusted with the potentiometer E, the relay will be 
switched on. The operating control LED flashes green. 
If the temperature difference falls below the set value 
by 1.6 K (non adjustable hysteresis), the controller de-
activates the relay.

For commissioning or maintenance work, the relay 
can be permanently energised by means of the manual 
mode. The manual mode can be activated or deactivated 
respectively with DIP switch 1. If the manual mode is 
active, the operating control lamp flashes red and green.

3.4 

Manual mode

3.5 

Maximum temperature limitation

With DIP switch 2, the temperature limitation can be 
activated as a maximum temperature limitation. The 
limit temperature can be adjusted by means of the po-
tentiometer C. The sensor connected to the terminals 
S2 is used as the reference sensor.  If the store tem-
perature reaches the adjusted maximum temperature, 
the store will no longer be loaded in order to avoid 
damage caused by overheating.  If the store tempera-
ture exceeds the maximum value, the operating con-
trol lamp flashes red.

3.6 

Antifreeze function

With DIP switch 3, the antifreeze function can be acti-
vated. The antifreeze function activates the loading cir-
cuit between the collector and the store when the col-
lector temperature falls below +4 °C. This will protect 
the fluid against freezing or coagulating. If the tempera-
ture at S1 r5 °C, the pump will be switched off.
When the antifreeze function is active, the operating 
control lamp flashes quickly.

Adjustment  range:  2 … 16 K
Factory setting: 6 K

Activated by default 
(DIP switch in ON position)
Adjustment  range:  20 … 90 °C
Factory setting: 60 °C

Deactivated by default 
(DIP switch in OFF position)

Note
Since this function uses the limited heat quantity of the store, the anti-
freeze function should be used in regions with few days of temperatures 
around the freezing point.

Deactivated by default
(DIP switch in OFF position)
Controller in automatic mode

C

ON

OFF

1

2

3

4

ON

OFF

1

2

3

4

ON

OFF

1

2

3

4

A

ON

OFF

1

2

3

4

A

ON

OFF

1

2

3

4

ON

OFF

1

2

3

4

A

ON

OFF

1

2

3

4

Содержание DeltaSol AX HE

Страница 1: ...d this manual carefully to get the best performance from this unit Please keep this manual safe DeltaSol AX HE www resol com Manual en Differential temperature controller Manual for the specialised cr...

Страница 2: ...exclusively addressed to authorised skilled personnel Only qualified electricians should carry out electrical works Initial installation must be effected by the system owner or qualified personnel nam...

Страница 3: ...ntees a protection against dripping water 1 Overview 4 2 Installation 4 2 1 Mounting 4 2 2 Electrical connection 6 3 Operation and function 6 3 1 Flashing codes 6 3 2 DIP switches and potentiometres 6...

Страница 4: ...m temperature limitation Housing plastic PC ABS and PMMA Mounting wall mounting Indication Display 1 operating control LED Operation 3 potentiometres 4 DIP switches 1 jumper Protection type IP 20 DIN...

Страница 5: ...2 2 1 112mm 2 5 6 7 3 8 4 T4A fuse Mains connection Relay load Grounding terminal common terminal block Sensor 1 2 PWM output DIP switches Switch on temperature difference potentiometre Temperature li...

Страница 6: ...normally closed contact 9 neutral conductor N Grounding terminal common terminal block Speed control of a HE pump is possible via a PWM signal The pump has to be connected to the relay power supply as...

Страница 7: ...the manual mode is active the operating control lamp flashes red and green 3 4 Manual mode 3 5 Maximum temperature limitation With DIP switch 2 the temperature limitation can be activated as a maximum...

Страница 8: ...eresis below the adjusted temperature difference the pump will be switched off S1 Collector sensor S2 Store sensor RO Solar pump ON OFF 1 2 3 4 C Deactivated by default DIP switch in OFF position de f...

Страница 9: ...cuit return preheating Use grounding terminals The controller calculates the temperature difference between collector sensor S1 and store sensor S2 If the difference is larger than or identical to the...

Страница 10: ...nce falls by 1 6K non adjust able hysteresis below the adjusted temperature differ ence the pump will be switched off S1 Solid fuel boiler sensor S2 Store sensor RO Circulating pump 5 Accessories SP10...

Страница 11: ...nnected temperature sensors can be checked with an ohmmeter Please check if the resistance values correspond with the table C F Pt1000 C F Pt1000 10 14 961 55 131 1213 5 23 980 60 140 1232 0 32 1000 6...

Страница 12: ...r the completeness of the drawings and texts of this manual they only represent some examples They can only be used at your own risk No liability is assumed for incorrect incomplete or false informati...

Отзывы: