Resol DeltaSol AX HE Скачать руководство пользователя страница 10

10

en

4.4 

Store loading by means of a solid fuel boiler

7

RO RC N N L

8 9 10 11

2

2

2

3

3

S1

RO

S2

 Use grounding terminals!

The controller calculates the temperature difference 
between solid fuel boiler sensor S1 and store sensor 
S2. The relay (RO) is energised when both switch-on 
conditions are fulfilled:
•  the temperature difference has exceeded the switch-

on value

•  the temperature at the solid fuel boiler sensor has 

exceeded the minimum temperature

If the temperature difference falls by 1.6 K (non-adjust-
able hysteresis) below the adjusted temperature differ-
ence, the pump will be switched off.

S1  =  Solid fuel boiler sensor
S2  =  Store sensor
RO  =  Circulating pump

Accessories

SP10 Overvoltage 

protection device

HR230 Auxiliary relay

Troubleshooting

Spare fuse 
(inside the cover)

In the case of an error, please check the following:

Check the supply line and recon-

nect it.

The fuse of the controller could be 

blown. The fuse holder (which holds 
the spare fuse) becomes accessible 
when the cover is removed.The fuse 
can then be replaced.

Check the power supply of the controller. Is it disconnected?

no

yes

Mains

C

ON

OFF

1

2

3

4

E

ON

OFF

1

2

3

4

A

ON

OFF

1

2

3

4

Содержание DeltaSol AX HE

Страница 1: ...d this manual carefully to get the best performance from this unit Please keep this manual safe DeltaSol AX HE www resol com Manual en Differential temperature controller Manual for the specialised cr...

Страница 2: ...exclusively addressed to authorised skilled personnel Only qualified electricians should carry out electrical works Initial installation must be effected by the system owner or qualified personnel nam...

Страница 3: ...ntees a protection against dripping water 1 Overview 4 2 Installation 4 2 1 Mounting 4 2 2 Electrical connection 6 3 Operation and function 6 3 1 Flashing codes 6 3 2 DIP switches and potentiometres 6...

Страница 4: ...m temperature limitation Housing plastic PC ABS and PMMA Mounting wall mounting Indication Display 1 operating control LED Operation 3 potentiometres 4 DIP switches 1 jumper Protection type IP 20 DIN...

Страница 5: ...2 2 1 112mm 2 5 6 7 3 8 4 T4A fuse Mains connection Relay load Grounding terminal common terminal block Sensor 1 2 PWM output DIP switches Switch on temperature difference potentiometre Temperature li...

Страница 6: ...normally closed contact 9 neutral conductor N Grounding terminal common terminal block Speed control of a HE pump is possible via a PWM signal The pump has to be connected to the relay power supply as...

Страница 7: ...the manual mode is active the operating control lamp flashes red and green 3 4 Manual mode 3 5 Maximum temperature limitation With DIP switch 2 the temperature limitation can be activated as a maximum...

Страница 8: ...eresis below the adjusted temperature difference the pump will be switched off S1 Collector sensor S2 Store sensor RO Solar pump ON OFF 1 2 3 4 C Deactivated by default DIP switch in OFF position de f...

Страница 9: ...cuit return preheating Use grounding terminals The controller calculates the temperature difference between collector sensor S1 and store sensor S2 If the difference is larger than or identical to the...

Страница 10: ...nce falls by 1 6K non adjust able hysteresis below the adjusted temperature differ ence the pump will be switched off S1 Solid fuel boiler sensor S2 Store sensor RO Circulating pump 5 Accessories SP10...

Страница 11: ...nnected temperature sensors can be checked with an ohmmeter Please check if the resistance values correspond with the table C F Pt1000 C F Pt1000 10 14 961 55 131 1213 5 23 980 60 140 1232 0 32 1000 6...

Страница 12: ...r the completeness of the drawings and texts of this manual they only represent some examples They can only be used at your own risk No liability is assumed for incorrect incomplete or false informati...

Отзывы: