Resistron RES-430 Скачать руководство пользователя страница 25

Startup and operation

RES-430

25

9.5.4

Temperature sensor

The maximum permissible temperature of the sensor
can be set with step 246 (assuming the temperature
sensor has been activated with step 241). An alarm is
immediately output by the controller if this maximum
temperature is exceeded.

If a heatsealing cycle is in progress, it is interrupted.
The temperature monitoring function is activated 3s
after the controller is switched on.

If a temperature sensor is not connected (or if the
sensor connecting cable is defective), an alarm is
output by the controller after 3s (assuming the tempe-
rature sensor has been activated with step 241).

The sensor temperature measurement
described here serves to monitor and/or limit

the load cell or machine temperature. It cannot be
used to monitor the temperature of the heatsealing
band or for temperature control.

9.6

Heatsealing band

9.6.1

General

The heatsealing band is a key component in the control
loop, since it is both a heating element and a sensor.

The geometry of the heatsealing band is too complex to
be discussed at length here. We shall therefore only
refer to a few of the most important physical and elec-
trical properties:
The measuring principle applied for this system neces-
sitates a heatsealing band alloy with a suitable tempe-
rature coefficient TCR, i.e. one whose resistance
increases as the temperature rises.
Too low a TCR leads to oscillation or uncontrolled hea-
ting.
When heatsealing bands with a higher TCR are used,
the controller must be calibrated for this.
The first time the heatsealing band is heated to appro-
ximately 200…250°C, the standard alloy undergoes a
once-only resistance change (burn-in effect). The cold
resistance of the heatsealing band is reduced by appro-
ximately 2…3%. However, this at first glance slight
resistance change results in a zero point error of
20…30°C. The zero point must therefore be corrected
after a few heating cycles (

section 9.6.2 "Burning in

the heatsealing band" on page 25).
One very important design feature is the copper or
silver-plating of the heatsealing band ends. Cold ends
allow the temperature to be controlled accurately and
increase the life of the teflon coating and the heatse-
aling band.

An overheated or burned-out heatsealing
band must no longer be used because the

TCR has been altered irreversibly.

9.6.2

Burning in the heatsealing band

If a new heatsealing band has been used, the zero
point is first of all calibrated while the band is still cold
by activating the "AUTOCAL" function on the controller.
When the "AUTOCAL" function has finished, the dis-
play shows the preselected calibration temperature
(default value: 20°C). Adjust the set point to approxi-
mately 250°C and press the "HAND" key (display in
home position) to activate the "START" signal and heat
for approximately 1 second. After recooling, the con-
troller usually indicates a value less than 20°C. Repeat
the "AUTOCAL" function. The heatsealing band has
now been burned in and the change in the alloying pro-
perties stabilized.
The burn-in effect described here does not occur if the
heatsealing band has already been thermally pre-
treated by the manufacturer.

RES-430

26

Temp. 

sensor

0V

27

ϑ

Maximum

Temperature

Time

Error message

sensor temp.

0

!

!

Содержание RES-430

Страница 1: ...omatic optimization AUTOTUNE Automatic phase angle compensation AUTOCOMP as of software revision 100 Automatic frequency adjustment Secondary control Heatsealing band alloy and temperature range selec...

Страница 2: ...interface temperature sensor 23 9 6 Heatsealing band 25 9 7 Startup procedure 26 10 Controller functions 28 10 1 Indicators and controls 28 10 2 Display 28 10 3 Navigation in the menus 30 10 4 Menu st...

Страница 3: ...guarantee trouble free operation of the RESISTRON temperature controller The temperature coefficient must be specified as follows e g Alloy 20 TCR 1100 ppm K NOREX TCR 3500 ppm K The RESISTRON tempera...

Страница 4: ...tall additional components are excluded from the warranty Warranty claims must be examined in the factory and approved by ROPEX 2 Application This RESISTRON temperature controller is an integral part...

Страница 5: ...system High precision thanks to further improved control accuracy and linearization of the heatsealing band characteristic High flexibility Secondary voltage range from 12V to 42V current range from 2...

Страница 6: ...cable Kap 13 How to order auf Seite 50 5 2 1 Scope of supply installation The serial piggyback module is supplied with spacers for installation on the motherboard of the RES 430 Proceed as follows to...

Страница 7: ...UAL temperature closing force You can also export the data as a CSV file for further processing in another PC program In addition the software permits the values in the Con figuration and Settings men...

Страница 8: ...1100ppm Alloy 20 0 300 C Heatsealing band voltage secondary voltage of impulse transformer 12 42VAC Max load current max secondary cur rent of impulse trans former Terminals 5 6 7 8 Two heatsealing ba...

Страница 9: ...Power dissipation max 40W Ambient temperature 5 45 C Degree of protection Motherboard IP00 Display terminal Front IP42 IP65 with transparent front cover Art No 887000 Back IP20 Installation Motherboar...

Страница 10: ...m must be used to fasten the printed circuit board on the underside All national and interna tional regulations must be complied with Connector Piggyback module 6 x fixing hole optional data interface...

Страница 11: ...l cutout RES 430 11 7 2 Display terminal 144 72 Outline dimensions of front frame Panel cutout 138 x 68 0 2 0 2 4 58 9 136 66 144 Front panel Connecting cable length 250mm Rubber seal Mounting clamp C...

Страница 12: ...ite 12 must be heeded additionally Check the tightness of all the system connec tions including the terminals for the impulse transformer windings 6 Make sure that the wiring conforms to the relevant...

Страница 13: ...wiring ROPEX Application Report Do not run the filter supply wires line side parallel to the filter output wires load side RESISTRON temperature controller RES 430 Impulse Transformer Designed accord...

Страница 14: ...rrent cable in order to avoid malfunctions or damage of the controller Step 240 in the Configuration menu must be set to Double for this purpose Band 1 Band 2 Heatsealing band Load cell interface and...

Страница 15: ...temperature sensor IMPORTANT If only ONE heatsealing band is used output terminals 7 8 must be jumped with a high current cable in order to avoid malfunctions or damage of the controller Step 240 in t...

Страница 16: ...on 9 1 View of the controller 9 1 1 Motherboard 9 1 2 Front view of the terminal Connector for terminal Terminals Nameplate Terminals Connector for piggyback module optional data interface Nameplate C...

Страница 17: ...ler settings can be reset to the fac tory settings with step 202 in the Configuration menu Only the language setting step 201 in the Configura tion menu remains unchanged Please refer to section 11 Fa...

Страница 18: ...If time control is on activating the START signal starts the internally parameterized timeout This timeout com prises Starting delay delay at the beginning of the heating phase Heating phase heating...

Страница 19: ...d as the factory setting In this case the heating process begins as soon as the START signal is activated 9 3 3 Setting the heatsealing time The heatsealing time can be set in the range from 0 to 99 9...

Страница 20: ...ling phase of the internal timeout ends when the ACTUAL temperature falls to the specified per centage of the SET temperature This value can be set between 40 and 100 The factory setting is 40 3 Cooli...

Страница 21: ...relay K1 or the sole noid drive closes at the end of the heating phase and opens again at the end of the cooling phase This configuration permits air cooling to be activated with relay K1 or the sole...

Страница 22: ...emperature The dia gnosis ends at the end of the parameterized heatse aling phase As of software revision 008 The temperature diagnosis function can be activated and deactivated with step 217 in the C...

Страница 23: ...uipment temperature or the temperature of the load cell An alarm is output by the controller if the maximum permissible temperature is exceeded The settings for the load cell interface and the tempera...

Страница 24: ...ivated during the closing movement of the sealing jaws for instance 3 End of heating phase A single force diagnosis takes place at the end of the heatsealing phase 4 End of cooling phase A single forc...

Страница 25: ...alibrated for this The first time the heatsealing band is heated to appro ximately 200 250 C the standard alloy undergoes a once only resistance change burn in effect The cold resistance of the heatse...

Страница 26: ...ons are described below 1 Switch off the line voltage and verify that all circuits are deenergized 2 The supply voltage specified on the nameplate of the controller must be identical to the line volta...

Страница 27: ...sfully the main menu appears on the display again Then specify a defined temperature heatse aling temperature with step 101 in the Settings menu and activate the START signal HEAT Alternatively you ca...

Страница 28: ...he display for appro ximately 2 seconds when the controller is switched on This message also includes details of the software ver sion ENTER HAND RESET ROPEX RESISTRON RES 4 MENU key for advancing to...

Страница 29: ...ure on page 32 10 2 4 Error message The fault diagnosis function of the controller is always active If a fault is detected it is indicated on the display immediately in the form of an error message se...

Страница 30: ...here in the menu structure providing a controller alarm is not active In this case the Alarm menu is opened instead If the display is in the home position or an alarm is indi cated and you press the M...

Страница 31: ...pressing the MENU key 2s You can then activate the AUTOCAL function by pressing the ENTER key section 10 8 Automatic zero cali bration AUTOCAL on page 36 If you press the MENU key for longer than 2s...

Страница 32: ...n 213 Lock HAND key 207 Set point reached 205 Temperature range Settings Configuration 1 Force sensor active 2 Force sensor not active 3 Time control OFF 4 Time control ON 5 TCR not variable 6 TCR var...

Страница 33: ...rce tare Configuration 1 Force sensor or force and tem perature sensor active 2 Temp sensor active 3 No sensors active 4 Temp sensor not active 243 Maximum force 1 2 249 Foot switch hold time Continue...

Страница 34: ...page 16 or section 10 4 Menu structure on page 32 Menu Menu step Numbering up to SW revision 006 Numbering as of SW revision 007 Settings menu Heatsealing temperature 1 101 Starting delay 3 103 Heatse...

Страница 35: ...ce it has been entered 10 7 Temperature indication actual value output If the display is in the home position the ACTUAL tem perature is indicated there as a digital value and as a dynamic bar The hea...

Страница 36: ...g the ENTER key The initial temperature ambient temperature of the heatsealing bar s which is currently valid for calibration can be set beforehand in the 0 40 C range using the UP and DOWN keys The z...

Страница 37: ...mong other things this permits the closing movement of the sealing jaws to be started by briefly activating and deactivating the FOOT SWITCH signal The hold time is deactivated if the value entered is...

Страница 38: ...troller you must set Double with step 240 The controller will otherwise be over loaded and damaged beyond repair If you change the configuration with step 240 you must run the AUTOCAL func tion with s...

Страница 39: ...after the AUTOCAL function has been successfully executed section 10 8 Auto matic zero calibration AUTOCAL on page 36 The interval after the end of the AUTOCAL func tion must be less than 2 0s Start A...

Страница 40: ...dication and value selection in Celsius C 2 Fahrenheit Temperature indication and value selection in Fahrenheit F Up to and including software revision 101 only Celsius C can be specified on the contr...

Страница 41: ...nge spe cified in section 6 Technical data on page 8 If a line voltage which is less than the lower limit of the permissible range occurs the controller is switched to a standby mode No more heatseali...

Страница 42: ...switch can then be opened again but the jaws remain closed 3 The heating process must begin immediately wit hout a starting delay 4 The heatsealing time t2 1s must begin when the ACTUAL temperature r...

Страница 43: ...ld be undertaken in the specified order Then ACTUAL temp START signal 180 C t t OFF 0 80 C 1s t Open Relay K1 Closed 95 of 180 C ON FOOT SWITCH OFF ON signal t Step in Configuration menu Setting 210 C...

Страница 44: ...re offered for this purpose in the 0 10VDC range each of which is assigned an error code section 10 21 Error messages on page 44 If a state that requires AUTOCAL occurs or if the con troller configura...

Страница 45: ...ure too high sec 9 4 Frequency fluctuation inadmissible line frequency Heatup time exceeded sec 9 4 1 Force sensor measure range overflow sec 9 5 3 Force sensor measure range underflow sec 9 5 3 Closi...

Страница 46: ...pulse transformer incorrectly sized Temperature too low Temperature too high Calibration failed loose contact ambient temperature fluctuations Data error Current signal incorrect calibration not possi...

Страница 47: ...ult replace controller Partial short circuit delta R Heatsealing band partially bypassed by conducting part clamp opposite heatsealing bar etc Parallel circuit interrupted Wire break heatsealing band...

Страница 48: ...riable temp coeff 1100ppm Step 205 Temperature range 300 C Step 206 Maximum temperature 300 C Step 207 Set point reached 10K Step 208 Set point exceeded 10K Step 210 Cooling mode Absolute Step 211 Sta...

Страница 49: ...is way 3 Restore customer settings Selecting this option restores the customer set tings that were saved as described in 2 When the controller is first delivered the customer settings are identical to...

Страница 50: ...s connector plug in parts and T 430 terminal Line filter LF 06480 Continuous current 6A 480VAC Art No 885500 Impulse transformer See ROPEX Application Report for design and ordering information Option...

Страница 51: ...Fuse 13 H HEAT 27 37 Heatsealing band type 8 Heatsealing time 19 Heatup timeout 23 Hold mode 38 Hold time for FOOT SWITCH signal 37 I Impulse heatsealing method 4 Impulse Transformer 13 Impulse transf...

Страница 52: ...n 35 Temperature range 8 18 Temperature sensor 9 23 Temperature setting 35 Temperature unit 40 Transformer 3 13 50 Type of construction 8 U Undervoltage detection 41 V View 16 Visualization software 7...

Отзывы: