INSTALLATION INSTRUCTIONS

34-00032EF-03

DB7110U Universal Heat Pump 
Defrost Controller

APPLICATION

The DB7110U Universal Heat Pump Defrost Controller is 

a heat pump defrost control used in single stage heat 

pump appliances. This product replaces over 260 OEM 

and competitive controls and can be easily programmed 

to meet the requirements of virtually any single stage 

heat pump. See Table 2, “Compatibility Chart.,” on 

page 5.

FEATURES

The DB7110U provides:

• Universal defrost control for single stage heat pumps

• LED display for easy setup and configuration

• Small, square footprint for easier installation

• Demand and timed defrost modes

• System status and fault indication

• Selectable reversing delay to limit noise when going 

in and out of a defrost cycle

• Fault history for easy troubleshooting

Fig. 1. DB7110U1000.

SPECIFICATIONS

Electrical Ratings

Input Voltage: 

24VAC, 60Hz

Max. Input Current: 

200mA

Compressor Contactor: 

1A @ 24VAC

Outdoor Fan:

1/2HP motor

5A full load, 30A locked rotor, 240VAC.

Aux Heat: 

1A @ 24VAC

Reversing Valve: 

1A @ 24VAC

All outputs rated for 100,000 operations.

All terminals except FAN-IN and FAN-OUT are NEC 

Class 2 low voltage.

Environmental Ratings

Operating Temperature Range: 

-40F to 150F

Humidity Limits: 

less than 95% (non-condensing)

INSTALLATION AND 
CONFIGURATION

Overview

When Installing This Product… 

1.

Read these instructions carefully. Failure to follow 

instructions can damage the product or cause a 

hazardous condition. 

2.

Check ratings given in these instructions and on 

the product to make sure the product is suitable 

for your application. 

3.

Installer must be a trained, experienced service 

technician.

4.

Use these instructions to check out the product 

operation after installation.

MENU

SETTING

SYSTEM

FAULT

M37637A

DB7110U-DEFROST CONTROL

Содержание DB7110U

Страница 1: ...leshooting Fig 1 DB7110U1000 SPECIFICATIONS Electrical Ratings Input Voltage 24VAC 60Hz Max Input Current 200mA Compressor Contactor 1A 24VAC Outdoor Fan 1 2HP motor 5A full load 30A locked rotor 240VAC Aux Heat 1A 24VAC Reversing Valve 1A 24VAC All outputs rated for 100 000 operations All terminals except FAN IN and FAN OUT are NEC Class 2 low voltage Environmental Ratings Operating Temperature R...

Страница 2: ...for example would correspond to a Termi nation Temperature of 60degF and an Enable Tem perature of 35degF 60deg 25deg 3 If the location of the OEM sensor thermostat is inaccessible or difficult to access place the new coil sensor on the coil loop nearest the expansion valve where refrigerant is entering the coil during the heating mode This location gives the largest temperature difference between...

Страница 3: ...ergency heat request from thermostat W requests will cause the AUX output to be energized Y Compressor request from thermostat Y requests will cause the COMPR and FAN terminals to be energized O Reversing valve request from thermostat controls the status of the RV output HPC 2 Terminals High pressure cutout switch these terminals must be shorted for compressor operation Never bypass protective pre...

Страница 4: ... enters defrost mode Fig 11 The reversing valve will change states and the aux heat will be energized A few moments later the fan will be turned off If Reversing Delay is enabled the compressor will be turned off for the selected time and then turn back on to reduce noise The DB7110U will remain in defrost for at least one minute After one minute has elapsed the DB7110U will exit defrost after the...

Страница 5: ... ICM320 ICM321 ICM322 ICM323 W1001 4 ICP 1052757 1069364 Interthem 6208800 Lennox 100269 01 100269 02 100269 04 100269 05 11K7101 1507N170027 29M0101 29M0201 30W87 33G9501 34M6301 46K67 56M3701 68I2901 68J8401 78H6801 84W8801 86G1601 97M81 LB 101263A LB 101263B 11K71 97M8101 30W8701 34M63 29M01 56M37 HPXB15 68I84 68I29 78H68 Nordyne 620880 621301A 621579B 621579C 624519A 624608 624626 624633 62464...

Страница 6: ...514 CNT02515 CNT02516 CNT02920 CNT02935 CNT03715 CNT03716 CNT04362 CNT04363 CNT04364 CNT04366 CNT04368 CNT04695 CNT05001 CNT05008 CNT05009 CNT05010 CNT05482 CNT05875 CNT1108 CNT01693 Weatherking 840 4 5548 White Rodgers 840 4 5548 47D40 801 47D43 101 47D43 111 47D43 11102 47D43 811 90 621 47D01U 843 York 031 00872 001 031 00872 002 031 00872 002 031 00872 701 031 00872 702 031 00872 703 031 01222 ...

Страница 7: ...umbered parameter has a selectable value according to the table below For example would represent Parameter 1 Defrost Enable Temperature set to 35 degF Display Description Current Fault s Present Right digits blank if there is no fault and to scroll through active faults Fault History and to scroll through history Press and hold for more than two seconds to clear all inactive faults Table 4 Config...

Страница 8: ...e Termination Temperature but a defrost cycle should never last longer than this time 8 14 minutes 14 minutes 8 Aux Heat Lockout Temperature W requests will be ignored if the outdoor temperature is higher than this temperature The Aux heat output will still function normally during a defrost cycle regardless of this setting Do not set this temperature below the Compressor Lockout Temperature or th...

Страница 9: ... for heat or cool ends Observe display for current operational mode Control displays current mode OFF HEAT or COOL If HEAT or COOL is shown after the call ended investigate thermostat wiring Unplug Y wire from control Display shows OFF compressor turns OFF Investigate thermostat wiring to ensure all wires are on the proper terminals Display shows OFF but compressor remains ON Check the wiring betw...

Страница 10: ...or no ice buildup Verify sensor placement and readings are correct Decrease the Enable Temperature to force the coil to get colder before a defrost is triggered Increasing this parameter too much can result in not triggering a defrost at all Verify coil readings with respect to this parameter Increase the Defrost Cycle Time to delay triggering a defrost Note this parameter has no effect if an outd...

Страница 11: ...lockage Check outdoor coil for blockage 6 Low Pressure Lockout LPC opened 3 times on a single request Investigate refrigerant charge 7 High Pressure Cutout is currently open Investigate refrigerant charge Check indoor coil for blockage Check outdoor coil for blockage 8 Low Pressure Cutout is currently open Investigate refrigerant charge 9 Coil Sensor Open Circuited Check the sensor hasn t become u...

Страница 12: ...uct is manufactured by Resideo Technologies Inc Golden Valley MN 1 800 468 1502 2019 Resideo Technologies Inc All rights reserved www resideo com Resideo Inc 1985 Douglas Drive North Golden Valley MN 55422 34 00032EF 03 M S Rev 09 19 Printed in United States ...

Страница 13: ...age Fig 1 DB7110U1000 SPÉCIFICATIONS Spécifications électriques Tension d entrée 24 V c a 60 Hz Intensité d entrée maximale 200mA Contacteur du compresseur 1 A à 24 V c a Ventilateur extérieur moteur HP 5A à pleine charge 30 A avec rotor bloqué 240 V c a Chauffage auxiliaire 1 A à 24 V c a Robinet inverseur 1 A à 24 V c a Toutes les sorties ont une capacité nominale de 100 000 opérations Toutes le...

Страница 14: ...e température de fin de cycle de 15 C 60 F et une température d activation de 1 6 C 15 6 C 14 C 60 F 60 F 25 F 3 Si l emplacement du capteur thermostat d origine est inaccessible ou difficile d accès placez le nouveau capteur de serpentin sur la boucle de serpentin la plus proche du détendeur où le réfrigérant pénètre dans le serpentin durant le mode de chauffage Cet emplacement procure la plus gr...

Страница 15: ...ntraîneront l excitation des bornes COMPR et FAN O Demande de robinet inverseur du thermostat contrôle l état de la sortie RV HPC 2 bornes Coupe circuit haut pression ses bornes doivent être court circuitées pour le fonctionnement du compresseur Ne jamais contourner les pressostats de protection LPC 2 bornes Contacteur de basse pression ces bornes doivent être mises en court circuit pour utiliser ...

Страница 16: ... sont sous tension 3 Maintenez le bouton enfoncé jusqu à ce que test apparaisse à l écran comme indiqué ci dessous Fig 10 4 Confirmez que l appareil passe en mode dégivrage Fig 11 Le robinet inverseur changera d état et le chauffage auxiliaire sera alimenté Quelques instants plus tard le ventilateur sera éteint Si le retard d inversion est activé le compresseur se désactivera pour la durée sélecti...

Страница 17: ... ICM318 ICM319 ICM320 ICM321 ICM322 ICM323 W1001 4 ICP 1052757 1069364 Interthem 6208800 Lennox 100269 01 100269 02 100269 04 100269 05 11K7101 1507N170027 29M0101 29M0201 30W87 33G9501 34M6301 46K67 56M3701 68I2901 68J8401 78H6801 84W8801 86G1601 97M81 LB 101263A LB 101263B 11K71 97M8101 30W8701 34M63 29M01 56M37 HPXB15 68I84 68I29 78H68 Nordyne 620880 621301A 621579B 621579C 624519A 624608 62462...

Страница 18: ...de l énergie Vous devez appuyer sur un bouton pour rallumer l écran Robertshaw DT2 1000 TD 10 SnyderGeneral 1395 329 CEBD430524 04B Tempstar ICP 1084 100 1084 83 1008 1087562 Therm O Disc 26E 10 Trane 21C14501G18 21C1450127 21C1450136 21C1450137 21C1450138 21C1450142 21C1450144 21C1450145 21C1450153 21C1450154 21C1450155 21C1450160 21C14282G01 CNT01106 CNT01108 CNT01129 CNT01152 CNT01431 CNT01510 ...

Страница 19: ...inutes 4 Temporisation de cycle court Durée d arrêt minimale entre les cycles du compresseur 0 à 5 minutes 3 minutes 5 Type de robinet inverseur Type O le robinet inverseur est excité en mode de climatisation B le robinet inverseur est excité en mode de chauffage O ou B O 6 Délai d inversion Temps d arrêt du compresseur lors de la commutation entre les modes de chauffage et de dégivrage Régler cet...

Страница 20: ...ornes du ventilateur sont raccordées à la tension secteur Vérifiez les pressostats du système Les bornes HPC et LPC intégrées doivent être en court circuit pour fonctionner Ne jamais contourner les pressostats de protection Vérifiez le capteur de serpentin Le système ne fonctionnera pas sans capteur de serpentin Le régulateur affiche DLY Le système est en retard de démarrage en raison d une protec...

Страница 21: ...égivrage ne sera jamais déclenché si la température du serpentin ne descend pas sous la température d activation Si la température d activation est trop élevée le système peut dégivrer inutilement Le système ne dégivre pas complètement Observez le cycle de dégivrage Le dégivrage commence trop tard Une trop grande quantité de glace est accumulée avant le début d un cycle de dégivrage Confirmez le b...

Страница 22: ...re d air extérieur est installé Le cycle de dégivrage dure trop longtemps La glace est fondue bien avant la fin du cycle Confirmez le bon positionnement du capteur et l exactitude des lectures Réduisez la température de fin de cycle pour terminer le cycle de dégivrage lorsque la température du serpentin est plus basse Réduisez la durée de dégivrage maximale pour forcer la fin du cycle de dégivrage...

Страница 23: ...e réfrigérant 7 Le coupe circuit haute pression est ouvert Vérifiez la charge de réfrigérant Vérifiez si le serpentin intérieur est obstrué Vérifiez si le serpentin extérieur est obstrué 8 Le coupe circuit basse pression est ouvert Vérifiez la charge de réfrigérant 9 Coupure dans le circuit du capteur de serpentin Vérifiez si le capteur s est débranché Vérifiez le câblage du capteur Remplacez le c...

Страница 24: ...e produit est fabriqué par Resideo Technologies Inc Golden Valley MN 1 800 468 1502 2019 Resideo Technologies Inc Tous droits réservés www resideo com 34 00032EF 03 M S Rev 09 19 Imprimé aux États Unis Resideo Inc 1985 Douglas Drive North Golden Valley MN 55422 ...