Operation
Installation and Start-up
36
Installation location
-
In reference / main living room of
the heating circuit (on an inside
wall of the room).
-
Not in the vicinity of radiators or
other heat dissipating units.
-
Any, if the room sensor influence
is switched off.
Installation
-
Remove cap from underside of
pedestal.
-
Secure the base at the installation
location.
-
Connect the electrical connection
cables.
-
Press the cap back on.
DCF receiver
Electrical connection: Connector
VII; 1,2
The controller has an optional
connection to a DCF receiver.
If the DCF receiver is connected, the
controller time is brought up to date
daily at 03.02 and additionally 5 minutes
after switching on the voltage.
If the time does not correct itself after
the specified period, select a different
location for the DCF (e.g. a different
wall) and restart the controller (switch
voltage-free once).
PC
All system-specific parameters can be
set and interrogated using the Comfort-
Soft parameterisation software. The
parameters can be saved, displayed
graphically and evaluated on the PC at
predefined intervals. T connect to a PC
you need the optical adapter or CoCo
PC active, which also supports the
sending of error messages by SMS and
the remote interrogation of controller
data.
Sensor resistances FBR
Temperature
+10 °C
680
Ω
9.950
Ω
+15 °C
700
Ω
7.855
Ω
+20 °C
720
Ω
6.245
Ω
FBR1
terminals 1-2
switch in position
q
FBR2
terminals 1-2
Room sensor
+25 °C
740
Ω
5.000
Ω
+30 °C
760
Ω
4.028
Ω