Operation
Overview of display values and settings
INSTALLATION
Designation
Value range
Default
IV
CODE-NO
0000 - 9999
Entry
CODE-NO
(Adjustment)
0000 - 9999
0000
BUS ID HS1
00 - 08
00
BUS ID 1
(- - - - ,00), 01-15
01
BUS ID 2
(- - - -), 02-15
02
BUS TERMINATI-
ON
00, 01 (OFF/ON)
01 (0631)
00 (1121)
AF SUPPLY
00,01
01 = ON
TIME MASTER
00, 01
00 = OFF
Expert area
Hinged cover OPEN
Î
search for
level on right with
Ç
, open with
Ä
These settings can only be changed if
the code no. is entered (see page 6).
E
If these values are set incorrectly,
they may cause malfunctions or
damage to the system.
CODE-NO
Entering the code number (see page 6)
allows all of the expert settings to be
modified => including the code number
itself (first parameter)
(
Ç
on right => CODE-NO 0000
Ä
=>
Ç
1st digit
Ä
=>
Ç
2nd digit
Ä
=>
Ç
3rd digit
Ä
=>
Ç
4th digit
Ä
=>
Ç
)
BUS ID HS1
For cascades, the HS are numbered
beginning with "01“. ("00“ = Single
boiler)
BUS ID1 / 2
(heating circuit number)
The heating circuits are sequentially
numbered starting with "01". heating
circuit numbers must not be assigned
twice. For replacement controllers,
please enter exactly the same heating
circuit numbers as the replaced
controller.
BUS TERMINATION
This parameter is used to switch the
terminal resistance for Can communi-
cation. The entire system may contain
exactly
one
terminating resistor.
Delivery state:
-
Mixer controller (1121) => „0“
(Parameter BUS ID HS1 > 00 =>
Bus terminator = 00)
E
When loading the factory settings,
the terminal resistance is newly set
(according to boiler sensor).
AF SUPPLY
(Outdoor sensor power
supply)
Switching off the power supply to the
outdoor sensor. Switching off allows up
to 5 controllers to be operated with a
single outdoor sensor. The power
supply must only be switched on if
there is one controller per sensor = "01".
TIME MASTER
(Only without or TIME
MASTER in system)
00 no time master => each heating
circuit has its own time
01 controller is time master => all
controllers and remote controls take
over the time settings of this controller.
!
No more than 1 TIME MASTER is
permitted in the system!
24