Operation
Overview of display values and settings
Guideline values
-
Underfloor heating
S = 0,4 bis 0,6
- Radiator
heating
S = 1,0 bis 1,5
ADAPTION (heat slope adaption)
Only active if an FBR analogue room
device is connected (room
operating mode selection) and an
outdoor sensor.
Function for automatic heat slope
setting
Starting Conditions:
- External
temperature
<
8°C
-
Operating mode is automatic
(I
or
II)
-
Duration of lowering phase at least
6 hours
At the beginning of the lowering period,
the current room temperature is
measured. During the next four hours,
this temperature is used as the set
point for the room regulator. The
heating curve is calculated from the
values determined during this time by
the regulator for the flow pipe nominal
temperature and the external
temperature.
!
If the adaptation is interrupted, e.g.
by a start-up discharge or the hot
water demand from an external
heating circuit, then the warning
triangle will appear in the display
until the function is carried out
successfully the next day or is
ended, e.g. by adjusting the
operating mode switch.
!
During the adaptation, the water
heating
and
the
heating
optimisation
of
the
regulator
are
blocked.
ROOMS-INFL (Room sensor
influence)
Only active if an FBR analogue room
device is connected (room
operating mode selection).
The heat generator temperature is
increased by the set value when the
temperature drops below the required
room temperature by 1K.
=> High values lead to fast control and
large heat generator temperature
fluctuations.
- - - -
=> pure weather-dependent control
0 =>
pure
weather-dependent
control
*)
20 => pure room temperature control
*) Special function with
ROOMS-INFL = 0
For one-off heating requirements during
the night reduction the heating pump
continues to run until the next heating
period is reached (see "Circulation
pump control").
ADAP ROOM-T (room sensor
adaptation)
For room control (e.g. with FBR), the
measurement can be corrected by
means of this setting should the room
sensor not measure correctly.
19