Impulse-guided circulation - Disable switch-on
After the running time of the circulation pump, the pump cannot be started again while disable switch on is
active. This prevents unnecessary permanent operation of the pump in the case of continuous dispensing. If
the hot water cools too much while disable switch-on is active, the time should be shortened.
Then select the desired time.
Menu item
Parameter
Factory setting
Impulse-guided circulation -
Disable switch-on
1 min - 15 mins
5 min.
Unmixed heating cycle
Optionally, you can activate or deactivate the "Unmixed cycle" function.
Menu item
Parameter
Factory setting
Unmixed heating cycle
Deactivated
Deactivated
Activated
Operating mode
Select the operating mode for the unmixed circuit.
Setting heating cycle mode
This is where you can select between the different
heating cycle modes
. The choice is between control
according to the set
"heating curve"
and
"fixed value regulation"
.
Menu item
Parameter
Factory setting
Operating mode unmixed cycle
Heating
As required
Cooling
Heating and cooling
After activating the unmixed mixed heating cycle, the 1st mixed heating cycle is enabled, and
after activating the 1st mixed heating cycle, the 2nd mixed heating cycle is enabled.
The descriptions of the 1st and 2nd mixed heating cycle are identical to the unmixed heating
cycle.
The mixed heating cycles each require a supply and return probe! These probes are included in the scope of
supply of the mixed REMKO heating cycle groups.
89