Operational malfunctions (continued)
Malfunction
Possible causes
Checks
Remedial measures
The compressor's
suction pipe and / or
liquid separator
have iced up
Thermal load has
increased
Is the outdoor unit in per-
manent operating mode?
Reduce the thermal load.
If necessary, install an
additional unit / insulate
components that have iced
up
Outdoor unit board malfunction display
Display
Error description
E0
EEPROM error, outdoor unit
E2
Communication error between indoor unit and outdoor unit
E3
Communication error between inverter board and control board
E4
Outdoor unit air inlet temperature probe faulty
E5
Over-voltage or under-voltage error
E8
Condenser fan speed control sensor not working
F1
Temperature of suction pipe for indoor unit A faulty
F2
Temperature of suction pipe for indoor unit B faulty
F3
Temperature of suction pipe for indoor unit C faulty
F4
Temperature of suction pipe for indoor unit D faulty
F5
Temperature of suction pipe for indoor unit E faulty
P1
High pressure fault
P2
Low pressure alarm
P3
Compressor current consumption too high
P4
Temperature probe for heat gas line faulty
P5
Excessive temperature in condenser
P6
Inverter board safety shut-down
LP
Ambient temperature too low
Note
After rectifying the fault, the malfunction code remains for 30 seconds (with the exception of E2 and E3).