Heating capacity SKT 790
0,00
0,50
1,00
1,50
2,00
2,50
3,00
3,50
4,00
4,50
5,00
5,50
6,00
6,50
7,00
7,50
8,00
8,50
9,00
9,50
10,00
-15
-7
-5
0
7
12
2
1
3
A
[°C]
Fig. 4: Performance curves, heating SKT 790 (data for room temperature 20 °C)
A: Outside temperature
1: COP
2: Heating capacity in kW
3: Power consumption in kW
Outside temperature in °C
-15
-7
-5
0
7
12
Heating capacity in kW
4.48
4.73
5.10
5.97
8.21
9.34
Power consumption in kW
1.92
1.94
1.99
2.07
2.27
2.31
COP
2.34
2.43
2.56
2.88
3.61
4.05
Cooling capacity SKT 790
0,00
0,50
1,00
1,50
2,00
2,50
3,00
3,50
4,00
4,50
5,00
5,50
6,00
6,50
7,00
7,50
8,00
8,50
9,00
21
25
30
35
40
2
1
3
A
[°C]
Fig. 5: Performance curves, cooling SKT 790 (data for room temperature FK 27 °C/TK19 °C)
A: Outside temperature
1: EER
2: Cooling capacity in kW
3: Power consumption in kW
Outside temperature in °C
21
25
30
35
40
Cooling capacity in kW
7.64
8.14
8.22
7.91
6.79
Power consumption in kW
1.92
2.07
2.26
2.47
2.50
EER
3.98
3.93
3.64
3.21
2.71
REMKO series SKT