5.6 Minimum clearances
Observe the minimum clearances to allow access for maintenance and repair work and facilitate optimum air
distribution.
b
a
E
C
A
B
F
1
b
a
A
B
C
D
E
2
1: Indoor unit (IT)
2: Outdoor unit (AT)
a: Air inlet
b: Air outlet
Measurements (mm)
A
B
C
D
E
F
RVT 265-355 DC IT
120
1500
120
-
150
2000
RVT 265-355 DC AT
300
2000
600
300
600
-
5.7 Connection variants for the indoor unit
The following connection variants can be used for the refrigerant, condensate and control lines.
D
C
D
B
A
C
A
B
Fig. 22: Connection variant (view from the rear)
A: Infeed of the refrigerant piping at the wall, left
B: Infeed of the refrigerant piping through the wall,
left
C: Outlet through the wall, right
D: Outlet at the wall, right (the refrigerant piping
must be bent through 180 degrees for this)
NOTICE!
A flare connection may only be established outside the room. Detachable, reusable connections are not
permissible inside!
31