Technical data
2.1 Unit data
Series
MXV 221
MXV 361
MXV 451
Operating mode
Wall chest for MVV outdoor units for cooling and
heating
Nominal cooling output
1)
kW
2.2
3.6
4.5
Nominal heat capacity
2)
kW
2.6
4.0
5.0
Application area (room volume), approx.
m
3
80
110
160
Adjustment range, room temperature
°C
+17 to +30
Operating range
°C/r.H.%
+17 to +32
Refrigerant
4)
R410A
Operating pressure, max.
kPa
4200
Air flow volume per stage
m³/h
229/345/430
229/430/510
400/512/660
Sound pressure level per stage
3)
dB (A)
26/32/38
27/33/39
36/39/42
Sound power level max.
dB (A)
57
57
59
Power supply
V/Ph/Hz
230/1~/50
Enclosure class
IP
X0
Electrical rated power consumption,
cooling
1)
W
20
25
35
Electrical rated power consumption,
heating
2)
W
20
25
35
Refrigerant connection
Injection pipe
Inches
(mm)
1/4 (6.35)
1/4 (6.35)
1/4 (6.35)
Refrigerant connection
Suction pipe
Inches
(mm)
1/2 (12.70)
1/2 (12.70)
1/2 (12.70)
Condensate drainage connection
mm
16
Dimensions H/W/D
600/700/210
Weight
kg
14.0
15.0
15.5
EDP no.
1623640
1623650
1623660
1)
Air inlet temp. TK 27 °C / FK 19 °C, outside temperature TK 35 °C, FK 24 °C, max. air flow volume,
5 m pipe length
2)
Air inlet temp. TK 20 °C, outside temperature TK 7 °C, FK 6 °C, max. air flow volume,
5 m pipe length
3)
Distance 1 m free field
4)
Contains greenhouse gas according to Kyoto protocol, GWP=2088