background image

n

Leak detection methods

The following leak detection methods are per-

mitted for systems with combustible refriger-

ants. Electronic equipment must be used for

detecting leaks. These must be selected with

the sensitivity matched to the situation and

recalibrated if necessary (calibration must take

place in a refrigerant-free environment). The

leak detection device must be adjusted to the

lowest flammability limit (LFL) of the refrig-

erant. Liquid leakage instruments are permitted

for most refrigerants. Chlorinated substances

are the exception here as the chlorine in com-

bination with the refrigerants can cause corro-

sion on the copper cables. If a leak is detected,

all potential open ignition sources must be

removed immediately. If a leak has been

detected in the system which requires

reworking of the piping in the form of soldering,

the system must be completely free of refrig-

erant or, if possible, the affected part discon-

nected from the system using stopcocks. The

affected system parts must be flushed with

oxygen-free nitrogen run before and during the

repair work.

n

Emptying and evacuating the system

If the refrigerant circuit must be opened for

repairs or other reasons, this must be carried

out in a safe and professional way. In any

event, proceed with extreme caution since igni-

tion may occur at any time! Stick to the fol-

lowing procedure:
1. Drain the refrigerant
2. Flush the system with insert gas
3. Evacuate
4. Repeat steps 2 to 3 if required
5. Opening the system by cutting or soldering
The system must be flushed with oxygen-free

nitrogen in order to guarantee safety. The

flushing process must be repeated multiple

times if necessary. Do not use compressed air

or oxygen for the flushing process! After evacu-

ating, flushing takes place by filling with dried

nitrogen until the operating pressure is reached

and then the system must be evacuated again.

This flushing process must often be repeated

until there is no more refrigerant in the system.

After the last flushing, the system must be

brought to the ambient pressure in order to

start work. The flushing process is indispen-

sable when soldering work is required on the

piping. Ensure that the vacuum pump outlet is

not near an ignition source and continuous

ventilation is guaranteed.

n

Filling process

The following requirements for the general

specifications must also be fulfilled during the

filling process:
- Ensure that no contamination occurs from

other refrigerants (residues in the filling equip-

ment).
- Keep the lines as short as possible to mini-

mise the likelihood of residues forming.
- Filling bottles and cylinders must be stood

upright.
- Ensure that the system is earthed before

filling.
- Label the system with the refrigerant type

designation after filling
- Never exceed the maximum fill level.
The system must be checked for leaks (pres-

sure test!) before filling. The system must be

checked for leaks once more after filling and

before commissioning. Check for leaks again

when leaving the work space.

n

Labelling when shutting down

If a unit must be taken out of operation and the

refrigerant must be disposed of, the unit must

be labelled with the date and a signature.

Ensure that the note remains attached to the

combustible refrigerant.

n

Transportation of units which contain com-

bustible refrigerants

National provisions must be observed.

n

Storing of units which contain combustible

refrigerant

National provisions must be observed.

n

Transportation without the original pack-

aging

If the units are transported without the original

packaging, they must be packed in such a way

that mechanical damage is prevented. The

units must be transported upright.

1.9  Unauthorised modification

and changes

Modifications or changes to units and components

are not permitted and may cause malfunctions.

Safety devices may not be modified or bypassed.

Original replacement parts and accessories

authorised by the manufactured ensure safety. The

use of other parts may invalidate liability for

resulting consequences.

 

 

 

 

 

9

Содержание MKT 255 ECO S-Line

Страница 1: ...on instructions Read the instructions prior to performing any task REMKO MKT ECO series MKT 255 ECO MKT 255 ECO S Line MKT 295 ECO MKT 295 ECO S Line Local room air conditioner in compact design 0233...

Страница 2: ...these operating instructions carefully before commis sioning using this device These instructions are an integral part of the system and must always be kept near or on the device Subject to modificati...

Страница 3: ...lation maintenance and inspection 7 1 9 Unauthorised modification and changes 9 1 10 Intended use 10 1 11 Warranty 10 1 12 Transport and packaging 10 1 13 Environmental protection and recycling 10 2 T...

Страница 4: ...n Repairs may only be carried out by authorised and certified specialist personnel n The unit must not be covered with plastic sheets n This unit must be disposed of professionally in accordance with...

Страница 5: ...RNING This combination of symbol and signal word warns of a potentially hazardous situation which if not avoided may be fatal or cause serious injury CAUTION This combination of symbol and signal word...

Страница 6: ...ters fireplaces is prohibited n The unit may only be installed operated and stored in rooms larger than 14 4 m2 n Protective covers grilles over moving parts must not be removed from units that are in...

Страница 7: ...oms with limited space is prohibited Ensure that sufficient space is available at the work place Ensure that the ambient conditions are suitable for working with combustible refriger ants n Identify r...

Страница 8: ...voided the critical points of potential refrig erant leakages must be checked using a leak detector The following notes must be observed when working on electronic components if the housing is changed...

Страница 9: ...ss must often be repeated until there is no more refrigerant in the system After the last flushing the system must be brought to the ambient pressure in order to start work The flushing process is ind...

Страница 10: ...nclude special agreements beyond these conditions In this case contact your contractual partner in the first instance 1 12 Transport and packaging The devices are supplied in a sturdy shipping con tai...

Страница 11: ...ting pressure cooling cycle kPa 1160 4120 Air flow volume per stage m3 h 230 290 325 260 330 340 Sound pressure level per stage 2 dB A 49 50 51 Sound power level max dB A 65 Power supply V Ph Hz 230 1...

Страница 12: ...densate pump located in the unit the con denser evaporates the condensate and discharges it to the outside via the exhaust air hose The unit filters and dehumidifies the air thereby creating a comfort...

Страница 13: ...Y or circulated air mode FAN The LEDs indicate the selected operating mode 3 FAN speed key With this key it is possible to set the fan speed and therefore the air flow It is possible to select between...

Страница 14: ...ith the unit switched on any change to the settings will be automatically transferred to the room air conditioner The proper receipt of data will be acknowledged with an audible beep n To operate the...

Страница 15: ...r supply must be of a sufficient cable size and must only be used fully rolled out Fig 5 Power supply n Check whether the stopper in the condensate drain is present and correctly installed There is a...

Страница 16: ...t air to the outdoor area or to outdoors Exhaust air routing variants You can route the exhaust air out of the building as follows Via a flat nozzle The flat nozzle supplied can be used in various dif...

Страница 17: ...evaporator fins This will transport the remaining moisture out of the unit and this will avoid unpleasant odours when the unit is re commissioned 2 Switch the unit off with the I O key pull out the po...

Страница 18: ...N1 CN2 L N PE M M M A 2 1 4 3 5 6 3 7 8 Fig 12 Electrical wiring diagram A Power supply 1 Infrared receiver 2 Liquid level switch 3 Temperature probe 4 Condensate pump 5 Fan motor evaporator 6 Compres...

Страница 19: ...The unit does not work or works at reduced cooling capacity Exhaust air hose kinked extended routed downwards or blocked Ensure that there is a clear path for the exhaust air Filter contamination inl...

Страница 20: ...n is not correctly inserted or is damaged Insert stopper correctly or replace if necessary Error indication by code Error code Error description Error elimination E1 Ambient temperature probe defec ti...

Страница 21: ...ou take out a mainte nance contract with an appropriate specialist firm This enables you to ensure the operational reli ability of the plant at all times Filter cleaning The unit is equipped with an a...

Страница 22: ...11 Exploded view of the unit and spare parts list 11 1 Exploded view of the unit MKT 255 ECO MKT 255 ECO MKT 295 ECO MKT 295 ECO Fig 14 Exploded view REMKO MKT ECO series 22...

Страница 23: ...er stopper 4 Sealing cap 5 Condensate pump 6 Protective cap 7 Condensate tray cover 8 Protection grid hose connection 9 Exhaust air hose connection nozzle 10 Liquid level switch 11 Compressor 12 Vibra...

Страница 24: ...41 Display board 42 Operating panel 43 Display circuit board 44 Display board cover 45 Housing front 46 Board housing cover 47 Board housing 48 Control board 49 Compressor capacitor 50 Capacitor compr...

Страница 25: ...ew 22 Exploded view of the unit 22 I Installation 15 M Maintenance 21 O Operation Control panel 13 R Recirculated air filter 15 S Safety Dangers of failure to observe the safety notes 5 General 4 Iden...

Страница 26: ...REMKO MKT ECO series 26...

Страница 27: ......

Страница 28: ...5232 606 260 E mail info remko de URL www remko de REMKO GmbH Co KG Klima und W rmetechnik Im Seelenkamp 12 32791 Lage Hotline within Germany 49 0 5232 606 0 Hotline International 49 0 5232 606 130 W...

Отзывы: