Function test of heating operating mode
1.
Open the on-site valves.
2.
Check all connections for leaks with suitable
leak detectors. If leaks are found, the faulty
connection must be remedied.
3.
Activate the main circuit breaker or fuse.
4.
Program the Smart-Control Touch.
5.
Switch on heating mode
Due to the turn on delay, the compressor
will start up a few minutes later.
6.
Check all regulating, control and safety
devices for function and correct adjustment
during the test run.
7.
Measure all cooling data and record the
measured values in the commissioning
report.
Final tasks
n
Use the Smart-Control Touch to set the target
temperature to the required value.
n
Mount all removed parts.
n
Familiarise the operator with the system.
NOTICE!
Check that the shut-off valves and valve caps
are tight after carrying out any work on the
cooling cycle. Use appropriate sealant products
as necessary.
Adding refrigerant
DANGER!
Work on the cooling circuit may be undertaken
only by trained specialist personnel! (technical
specialist category I)
DANGER!
Only refrigerant in a liquid state may be used to
fill the cooling cycle!
CAUTION!
Danger of injury from refrigerant!
Refrigerant degreases the skin on contact and
may cause cold burns.
Therefore:
- Wear chemical-resistant protective gloves
when undertaking any work involving refriger-
ants.
-Safety glasses must be worn to protect the
eyes.
NOTICE!
Check the overheating to determine the refrig-
erant fill quantity.
NOTICE!
The escape of refrigerant contributes to climatic
change. In the event of escape, refrigerant with
a low greenhouse potential has a lesser impact
on global warming than those with a high
greenhouse potential. This device contains
refrigerant with a greenhouse potential of 1975.
That means the escape of 1 kg of this refrig-
erant has an effect on global warming that is
1975 times greater than 1 kg CO
2
, based on
100 years. Do not conduct any work on the
refrigerant circuit or dismantle the device -
always enlist the help of qualified experts.
51