Condensate drainage connection and safe
drainage - strip foundation
2
3
7
5
1
9
10
10
4
4
8
8
6
Fig. 38: Condensate drainage, seepage of conden-
sate and strip foundation (cross-section)
1:
Heat pump (air outlet)
2:
Vibration dampers
3:
Floor bracket (accessory)
4:
Reinforced strip foundation, frost free
5:
Gravel layer for seepage
6:
Protective tube for lines and
electrical connecting line
(temperature resistant up to at least 80 °C)
7:
Drainage channel
8:
Frost line
9:
Drainage pipe
10: Soil
NOTICE!
When installing an LWM-Duo heat pump, the
minimum distances must be observed and an
air short circuit must be prevented.
A D
C
4
4
E
B
B
1
9
5
5
Fig. 39: Dimensions for the strip foundation (bird's
eye view)
1: Heat pump
4: Reinforced strip foundation, frost free
5: Gravel layer for seepage
9: Drainage pipe
dimensioning the strip foundation
(all dimensions in mm)
Dime
nsion
LWM 80
LWM 110
LWM 150
A
1000
1000
1000
B
200
200
200
C
840
840
840
D
700
700
700
E
600
600
600
NOTICE!
Anti-freeze protection
In the case of heat pump systems, in which
frost-free conditions are not assured, a
drainage facility should be provided. If control
and heating circulation pump are ready for
operation, the anti-freeze protection function of
the controller works. The system must be emp-
tied when the heat pump is shut down or there
is a power failure. For heat pump systems in
which a power failure cannot be detected (e.g.
holiday home), the heating circuit must be oper-
ated with a suitable anti-freeze protection.
REMKO LWM series
40