2
Technical data
2.1 Unit data
Unit type
Symbol
Unit
ELT 40
Nominal heat capacity
P
nom
kW
36
Minimum heat capacity
P
min
kW
15
Maximum continuous heating power
P
max,c
kW
36
Switchable heating capacity
kW
15/30/36
Air volume
m
3
/h
4250
Temperature increase (
r
t
) max.
K
65
Power supply
V/Hz
400/3~/50
Max. rated current
A
55
Max. power consumption
kW
37.5
Auxiliary current consumption at nominal heating
power
el
max
kW
37.5
Auxiliary current consumption at minimum heating
power
el
min
kW
16.5
Auxiliary current consumption in standby condition
el
SB
kW
0.005
Fuse protection (provided by the customer,
slow-blow)
A
64
Sound pressure level, LpA 1m
1)
dB(A)
74
Dimensions (length/width/height)
mm
1410/560/775
Type of room temperature control
electronic (external)
Weight
kg
81.5
EDP no.:
114800
1)
Noise level measurement DIN 45635 - 01 - KL 3
We reserve the right to modify the dimensions and design as part of the ongoing technical development
process.