Access to the expert level
In order to access the expert level, the Easy-Control remote control must be deactivated with the “ ” key.
Once the remote control has been deactivated, press the “M" key and “ ” key at the same time for approx.
five seconds.
The expert level is now released and starts with the parameter “1” from the following table.
With the “M” key you can now display the individual parameters in order.
Change the parameters using the arrow keys “ ” and “ ”.
Parameter
Function
Value range
Factory setting
User settings
1
Correction of the
room temperature
"-9 °C - + 9 °C
"-2 °C"
2
Switching hysteresis
"1 °C - 5 °C"
"1 °C"
3
Key lock
0: Key lock apart from
“on / off”
1: All keys locked
1
4
Probe type
In: Internal probe of
the remote control
Ex: External probe
AL: Internal and
external probe
AL
Factory setting
5
Min. temperature
"+5 °C - +15 °C"
5 °C
6
Max. temperature
"+15 °C - +45 °C"
35 °C
7
Time 12/24 hrs.
0: 12 hrs
1: 24 hrs
1
8
Temperature display
0: measured room
temperature
1: Room target tem-
perature
0
9
Max. room set tem-
perature
"25 °C - 70 °C"
45 °C
A
Min. room set temper-
ature
"0 °C - 10 °C"
10 °C
b
Display brightness
Display brightness in
stand-by mode
0 (dark) - 99 (light)
c
BUS address
"01 - 99"
1
d
Band
"01 - 06"
1
Factory setting
After the settings are entered, it is not necessary to save the parameters. The data is accepted automatically.