2
Technical data
2.1 Units data
Series
CMF 120 CMT 120 CMF 160 CMT 160
Function
Heating or Cooling
System
Split-Air/Water
Heat pump manager
Multitalent or Multitalent Plus
Storage tank for hydraulic decoupling of volumetric
flows
on-site
series
160 l
on-site
series
160 l
Electric booster heating / rated output
kW
optional
series / 6
optional
series / 6
Drinking water heating (switching valve)
optional
series
optional
series
Heating capacity min / max
kW
3,5 - 11,0
5,0 - 16,0
Heating capacity / compressor frequency / COP
1)
for A10/W35
kW/Hz/
COP
10,5 / 99 / 4,4
15,3 / 76 / 4,7
Heating capacity / compressor frequency / COP
1)
for A7/W35
kW/Hz/
COP
10,0 / 96 / 4,3
13,0 / 77 / 4,4
Heating capacity / compressor frequency / COP
1)
for A2/W35
kW/Hz/
COP
7,2 / 96 / 3,4
9,6 / 76 / 3,2
Heating capacity / compressor frequency / COP
4)
for A2/W35
kW/Hz/
COP
5,1 / 61 / 3,9
6,9 / 51 / 3,4
Heating capacity / compressor frequency / COP
1)
for A-7/W35
kW/Hz/
COP
4,8 / 99 / 2,5
8,2 / 77 / 2,6
Heating capacity / compressor frequency / COP
1)
for A-15/W35
kW/
Hz/
COP
3,8 / 99 / 1,9
5,4 / 77 / 1,7
Heating capacity / compressor frequency / COP
1)
for A7/W45
kW/Hz/
COP
9,4 / 99 / 3,4
13,3 / 76 / 3,4
Heating capacity / compressor frequency / COP
1)
for A2/W45
kW/Hz/
COP
7,0 / 96 / 2,8
9,3 / 76 / 2,5
Heating capacity / compressor frequency / COP
1)
for A-7/W45
kW/Hz/
COP
5,2 / 99 / 2,2
7,4 / 77 / 1,9
Heating capacity / compressor frequency / COP
1)
for A-15/W45
kW/
Hz/
COP
4,3 / 116 / 1,5
4,6 / 77 / 1,2
Heating capacity / compressor frequency / COP
1)
for A20/W55
kW/Hz/
COP
10,4 / 94 / 3,0
12,9 / 61 / 3,4
Heating capacity / compressor frequency / COP
1)
for A7/W55
kW/Hz/
COP
7,9 / 89 / 2,5
9,4 / 61 / 2,5
Heating capacity / compressor frequency / COP
1)
for A-7/W55
kW/Hz/
COP
3,1 / 95 / 1,1
6,1 / 77 / 1,3
Cooling capacity / compressor frequency / EER
2)
for A35/W7
kW/Hz/
EER
5,4 / 70 / 2,9
12,1 / 74 / 3,1
Cooling capacity / compressor frequency / EER
2)
for A27/W7
kW/Hz/
EER
5,9 / 70 / 3,5
12,0 / 69 / 3,7
REMKO CMF/CMT
8