8.8 Auxiliary relays and contactor function
Auxil-
iary
relays
Function
Use ...
Found in the
circuit dia-
gram ...
K1
Controls the charge pump, circulating pump
heating circuits 1 and 2 and the relay K5
... in emergency heating
mode (Manual mode)
K1E
Activation of the flow monitor
... in emergency heating
mode (Manual mode)
K2
Ccontrols K5 and activates the flow fault E2
... in normal operation (Auto-
matic mode)
K3
Setting the heat pump demand (compressor).
Compressor ON, if K3 is deactivated and contact
on the control board is closed
... in normal operation (Auto-
matic mode)
CN 83.1 und 83.2
K4
CN
51.2
Setting the cooling release. Cooling ON if K4 has
activated and contact on the control board is open
... in normal operation (Auto-
matic mode)
CN 51.1
K5
Actuation of the switching valve for the 2nd
heating source. Makes the zero potential contact
available for the demand of the 2nd heating
source
... in normal operation (Auto-
matic mode)
K6
Electric heating contactor, level 1 (6 kW)
... in normal operation (Auto-
matic mode) and in emer-
gency heating mode (Manual
mode)
K7
External error message
... in normal operation (Auto-
matic mode)
K8
Electric heating contactor, level 2 (3 kW)
... in emergency heating
mode (Manual mode)
K10
Enabling of the fault input E2 of the heat pump
manager ("Heat pump fault" contact opening input
E2) after the indoor unit charging pump was
switched on
... in normal operation (Auto-
matic mode)
Fig. 56: Auxiliary relays