5.5 Condensate removal
In cooling mode:
The unit is equipped with automatic drainage of the
condensate water that arises while in cooling
mode. For this purpose, the water that arises is
collected in the condensate tray of the unit and dis-
persed by a pump on the condenser. Here, it evap-
orates and is fed outside with the aid of the
exhaust air.
If the unit is operated for a prolonged period of
time, or if it is operated at a very high outdoor air
humidity, it is possible that the quantity of conden-
sate water that arises is greater than the quantity
that can be evaporated. In this case, the unit
switches off via the integrated liquid level switch
and “OF” appears on the display.
NOTICE!
It is recommended to provide continuous con-
densate drainage even for cooling mode.
Beneath the unit there is a condensate drainage
connection for the permanent condensate drainage
connection and a T-piece with a closed emergency
drainage nozzle. Both connections are sealed at
the factory with a rubber stopper.
NOTICE!
In heating mode, automatic discharge through
evaporation is not possible and a permanent
condensate drain is absolutely necessary.
Emergency drainage
Hold a container (with a min. container capacity of
3 litres) beneath the unit and open the emergency
drainage to discharge. Then close off the emer-
gency drainage nozzle with the rubber stopper.
2
1
Fig. 8: Condensate removal
1: Emergency drainage nozzle
2: Connection for permanent discharge (13 mm)
17