6.5.6
Connecting the flue gas outlet and air supply
S Insertion depth 25 mm
1. Connect the flue gas outlet pipe and the air supply pipe to the boiler.
2. Fit the subsequent flue gas outlet pipes and air supply pipes in ac
cordance with the manufacturer's instructions.
Caution
The pipes must not be resting on the boiler.
Fit the horizontal parts sloping down towards the boiler, with a
gradient of 50 mm per metre.
6.6
Electrical connections
6.6.1
Control unit
The table gives important connection values for the control unit.
Tab.20 Connection values for control unit
Supply voltage
230 VAC/50 Hz
Main fuse value F1 (230 VAC)
6.3 AT
Fuse value F2 (230 VAC)
2 AT
Fan
230 VAC
Danger of electric shock
The following components of the boiler are connected to a 230 V
power supply:
Electrical connection to circulating pump.
Electrical connection to gas combination block.
Electrical connection to fan.
Control unit.
Ignition transformer.
Power supply cable connection.
The boiler has a three-wire mains lead (lead length 1.5 m) and is suitable
for a 230 VAC/50 Hz power supply with a phase/neutral/earth system. The
boiler is not phase sensitive. The power supply cable is connected to the
X1 connector. A spare fuse can be found in the housing of the control unit.
Caution
Always order a replacement mains lead from Remeha. The
power supply cable should only be replaced by Remeha, or by
an installer certified by Remeha.
The boiler switch must be easily accessible at all times.
The boiler has several control, protection and regulation connection op
tions. The standard PCB can be extended with optional PCBs.
For more information, see
Optional electrical connections, page 85
Fig.17
Connecting the flue gas outlet and
air supply
AD-0000034-01
80/125 mm
100/150 mm
S
6 Installation
30
123157 - v.12 - 07022018