6 Installation
6.1
General
Warning
The boiler must be installed by a qualified installer in accordance
with local and national regulations.
6.2
Preparation
6.2.1
Positioning the boiler
The fitting bracket on the back of the casing can be used to mount the
boiler directly on the suspension bracket.
The boiler is supplied with a mounting template.
1. Attach the mounting template of the boiler to the wall using adhesive
tape.
Warning
Use a level to check whether the mounting template is hanging
perfectly horizontally.
Protect the boiler against building dust and cover the connection
points for the flue gas outlet and air supply. Only remove this
cover to assemble the relevant connections.
2. Drill 2 holes of Ø 10 mm.
Important
The extra holes are intended for use in the event that one of the
two fastening holes is not suitable for correct fastening of the plug.
3. Fit the Ø 8 mm plugs.
4. Attach the suspension bracket to the wall with the Ø 10 mm bolts
supplied.
5. Mount the boiler on the suspension bracket.
6.3
Hydraulic connections
6.3.1
Rinsing the system
The installation must be cleaned and flushed in accordance with BS 7593
(2006) and BSRIA BG 33/2014.
Before a new boiler can be connected to an existing or new system, the
entire system must be thoroughly cleaned and flushed. This step is abso
lutely crucial. The flushing helps to remove residue from the installation
process (weld slag, fixing products etc.) and accumulations of dirt (silt,
mud etc.)
Important
Flush the system with a volume of water equivalent to at least
three times the volume of the system. Flush the DHW pipes with a
volume of water equivalent to at least 20 times the volume of the
pipes.
Fig.7
Mounting the boiler
AD-0000018-02
2
1
5
4
3
6 Installation
22
123157 - v.12 - 07022018
Содержание Quinta Pro 115