Caution
Provide a separate power supply for the pump and a power
switch, if necessary.
The output available per outlet is 450 W (2 A, with cos ϕ = 0.7)
and the inrush current must be less that 16 A. If the load exceeds
either of these values, the control must be relayed using a
contactor that must in no circumstances be installed in the control
panel. The sum of the currents from all outlets must not exceed
5 A.
5.3.4
Cable routing and access to the connection terminal
blocks
1. Unlock the front door.
2. Tilt and lift the door to remove it.
3. Remove the two screws and dismantle the rear top panel.
4. Unlock and open the cover on the control box.
Fig.20
MW-2000830-02
1
2
1
Fig.21
MW-2000831-01
3
Fig.22
MW-2000832-01
4
90º
5 Installation
22
MID _HMI T-control - Gas 120 ACE
7717201 - v03 - 25062019