INSTRUCTIONS FOR THE RELIANCE

 

PowerBack

 

TM 

Model THP108

 

  

Non-Contact Utility Power Return Alert 

THE  RELIANCE 

PowerBACK 

IS  NOT  FOR  “DO-IT-

YOURSELF”  INSTALLATION.    It  must  be  installed  by  a 
qualified  electrician  in  accordance  with  all  applicable 
electrical and building codes. 

This  Reliance  PowerBACK  is  a  non-contact  utility  power  return 
sensor with audible alert.  If the main circuit breaker in a generator-
ready  load  center  or  manual  transfer  panel,  has  to  be  turned  the 
OFF position in order for the standby generator to supply  power to 
the  circuits  within  the  panel,  the  PowerBACK,  when  activated,  will 
sound a 100dB audible alert when utility power is restored.  

The  Reliance  PowerBACK!  will  indicate  that  utility  power  has 
returned and the standby generator may be shut down.  

KEY  COMPONENTS  OF  THE  PowerBack  POWER 
RETURN ALERT 

1. 

Audible  alert  and  battery  enclosure  with  “System  Armed”  and 
“Low Battery” lights. 

2. 

23”  flexible  insulated  cable  attached  to  a  15”  flexible  current–
sensing antenna. 

3. 

A 36” ground wire 

INSTALLATION   

 

 

 

 

CAUTION!  The  PowerBACK!  is  an  isolated   low-voltage  device 
that  is  intended  to  come  in  contact  with  insulated  conductors 
feeding  a  residential  or  light  commercial  load  center  (circuit 
breaker  panel).   It  is  not  intended  for  use  on  uninsulated 
conductors such as busbars 

DANGER!    HAZARDOUS  VOLTAGE!  TURN  MAIN  CIRCUIT 
BREAKER TO THE OFF POSITION BEFORE INSTALLATION.  

DANGER! 

THE  LINE  TERMINALS  ON  THE  MAIN  CIRCUIT 

BREAKER  MAY  BE  LIVE  DURING  THE  INSTALLATION 
PROCESS. 

 

TAKE  ALL  APPROPRIATE  SAFETY  MEASURES 

DURNG  INSTALLATION.    IT  IS  RECOMMENDED  THAT 
INSTALLERS  CONTACT  THE  LOCAL  POWER  UTILITY  TO 
DEENERGIZE  THE  LOAD  CENTER  BEFORE  INSTALLING  THE 
PowerBACK.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

              IITHP108  022218 

 
9.  Carefully wrap the 15-inch flexible antenna in a tight coil around 
one of the main power cables feeding the main circuit breaker.  The 
antenna should be secured in the tight coil with electrical tape or a 
cable  tie  as  shown  in  the  photo.   

DANGER!  IF  THEY  HAVE  NOT 

BEEN  DEENERGIZED,  THE  LINE  TERMINALS  ON  THE  MAIN 
CIRCUIT BREAKER  WILL BE LIVE DURING THE INSTALLATION 
PROCESS.

 

10.  Strip the ground (green) wire and connect it to the ground bus in 
the loadcenter. 
11.    Replace  panel  cover,  turn  the  main  circuit  breaker  ON,  and 
reenergize the loadcenter. 

TESTING 

 

 

  

1.      Simply  turn  the  PowerBACK  on/off  switch  to  the  ON  position.  
The 100dB alert will sound. 
2.   Return the Power BACK on/off switch to the OFF position.   
The  red “Low Battery Indicator” will light when the battery needs to 
be replaced. 

OPERATION 

 

 

 

 

 

1.  When utility power fails, turn the PowerBACK on/off switch to the 
ON position.  The green “System Armed” light will come on. 
2.    Follow  the  instructions  on  the  generator-ready  load  center  or 
manual  transfer  panel  for  activating  the  link  to  the  standby  power 
system. 
3.  When utility power is available to the panel, the PowerBACK will 
emit a 100dB audible signal. 
4.  Turn the PowerBACK on/off switch to the OFF position. 
5.    Follow  the  instructions  on  the  generator-ready  load  center  of 
manual transfer panel to return utility power. 

TROUBLESHOOTING 

 

 

 

 

1.    PowerBACK  will  not  sound  alert  when  utility  mains  power  is 
available 
a.   Replace 9v battery with known good battery. 
b.  Assure that the sensing antenna is wound tightly around the main 

feeder cable.  Reposition sensing antenna if necessary.   

2.    PowerBACK  alerts  when  loadcenter  is  being  supplied  by 
generator power. 
a.   Assure that the ground wire is properly connected. 
b.   Assure that the sensing antenna (the white part) is not near any 

conductors that are energized by the generator 

c.    Re-route  the  flexible  cable  (the  black  part)  as  far  away  as 

possible  from  any  conductors  that  are  energized  by  the 
generator. 

CAUTION: Do not operate any generator in an enclosed 
area,  where  the  exhaust  fumes  can  accumulate  in  an 
enclosed area, or near open doors and windows

.                                                                 

SPECIFICATIONS 

 

Voltage range:  120 VAC maximum 

 

Frequency range:  50-60 Hz 

 

Installation/overvoltage category III.  Suitable for 
installation on insulated conductors of residential and light 
commercial load centers and panel boards. 

 

Pollution degree:  2 

 

Environmental condition: normal 

 

Altitude: 2,000 m (6,561 feet) maximum 

 

For indoor use only 

 

Operating temperature range:  5 

o

C to 40 

o

C (41 

o

F to 104 

o

F) 

 

Operating relative humidity:  80% RH or less 

 

UL Listed

 

Reliance Controls Corporation 
2001 Young Court 
Racine, Wisconsin  53404 
(262) 634-6155 

 

1.  Install  a  fresh  9V  alkaline 
battery  in  the  PowerBACK 
battery compartment.. 
2.    Move  Main  (Utility)  circuit 
breaker  handle  to  the  “OFF” 
position. 
3.Remove panel cover. 
4.    Locate  and  remove  a  ½” 
knockout  within  20  inches  of 
the  incoming  utility  power 
conductors. 
5.    Remove  the  retaining  nut 
from 

the 

PowerBACK 

threaded nipple. 
6.  Feed the flexible cable (the 
black  part)

 

and  antenna  (the 

white 

part) 

through 

the 

knockout from the

 outside. 

7.    Feed  the  flexible cable 
and  antenna  through  the 
retaining nut. 
8.  Fasten the PowerBACK 
to  the  enclosure  with  the 
retaining nut. 