Reliable Automatic Sprinkler Co., Inc.,

 103 Fairview Park Drive, Elmsford, New York 10523

Model RFS42
Residential Flat Concealed
Horizontal Sidewall Sprinkler
(SIN RA4835)

Bulle

tin 048 Ma

y 2022

Bulletin 048 May 2022

Coverage to 16 ft. x 20 ft. (4.9m x 6.1m) 

Features:

1. 

Flat cover plate for a flush, concealed wall finish.

2.  4.2 (60 metric) K Factor.
3. 

Sized  to  fit  in  a  3½”  or  larger  stud  space  even 

when installed directly in a TorqueSafe

TM

 90° 

Sprinkler Head Elbow** and several other com-

mon ½” and ¾” by ½” sprinkler fittings. 

4.  Push-on/pull-off flat cover plate.
5.  Sprinkler shipped complete with factory installed 

 

protective cap.

6. 

Sprinkler assembly and cover plate packaged sepa

-

rately.

7.   

1

/

8

” (3.2 mm) cover plate adjustment.

8.  Model RFS Cover plate available in a wide variety 

of colors and finishes.

Listings & Approvals

1.  Listed by Underwriters Laboratories Inc. and UL 

certified for Canada (cULus).

UL Listing Category

Residential Automatic Sprinklers

UL Guide Number

VKKW

Patents:

U.S. Patent No. 7,353,882, other Patents pending

Product Description

The Reliable Model RFS42 Concealed Residential Extended 

Coverage  Horizontal  Sidewall  Sprinkler  is  an  attractive,  con

-

cealed  sprinkler  assembly  specially  sized  to  fit  within  a  3½” 
or larger stud space. The sprinkler uses a push-on/pull-off flat 

cover plate assembly. The sprinkler assembly is shipped with a 
protective cap.  

 The flat cover plate is attached to the skirt using 135°F (57°C) 

ordinary temperature classification solder.  The sprinkler is in

-

stalled  into  the  sprinkler  fitting  using  the  Model  G6  Sprinkler 

Wrench.  

When the ambient temperature rises, the solder holding the 

cover plate melts, allowing the release of this part and thus ex

-

posing the sprinkler inside to the rising ambient temperature.

 This sprinkler is listed for a maximum service pressure of 175 

psi (12,0 bar).

Application and Installation

The Model RFS42 sprinkler is intended for installation in the 

residential portions of any occupancy in accordance with NFPA 
13, 13R & 13D. The sprinkler is listed as a Concealed Residen-

tial Horizontal Sidewall Sprinkler. System design and installation 
requirements for ceiling configurations are described in NFPA 

13, 13R or 13D, as applicable. 

The  minimum  listed  spacing  between  Model  RFS42  sprin

-

klers is 8 ft (2.4 m). 

The low flow RFS42RES sprinklers are specifically engineered 

to  meet  the  latest  residential  sprinkler  listing  standards  (UL 

1626 Standard).*

The sprinkler must be installed and properly oriented with the 

Model G6 Wrench:

Do not remove the factory installed plastic protective cap 

since it is sized to fit inside the G6 wrench. Note that the sprin

-

kler can only mate  when the sprinkler’s deflector orientation 

tab (Fig. 1) is aligned with wrench’s key-way. The G6 wrench 
is provided with bubble level pad and TOP marking, to allow 

the proper orientation of the horizontal sidewall deflector. Final 

leveling  can  be  done  after  leak  proof  joint  is  obtained  with  a 

minimum to maximum torque of 8 to 18 ft-lbs (11 to 24 N.m). 
Leave the protective cap on to protect the sprinkler while the 
wall is plastered, wallpapered or painted.  The protective cap 
must be removed and the listed cover plate installed prior to 

the sprinkler system being placed in service. A 2

5

/

8

” (67 mm) 

diameter hole must be cut in the wall for the sprinkler assembly 

to extend through.

Concealed cover plate/cup assemblies are listed only for use 

with specific sprinklers.  The use of any other concealed cover 

plate/cup assembly with the Model RFS42 Horizontal Sidewall 
Sprinkler or the use of this dedicated concealed cover plate as-

sembly on any sprinkler with which it is not specifically listed will 
void all guarantees, warranties, listings and approvals.

* Effective date 3/14/2008

**Spears Manufacturing Company